CORR/GUARD ADDENDUM 

4CGSWHVK & 4CGVSWHVK

INSTALLATION INSTRUCTIONS

IMPORTANT: 

DO  NOT  INSTALL  WITHOUT  FIRST  READING 

THESE INSTRUCTIONS VERY CAREFULLY.

These instructions pertain to the installation of the 4CGSWHVK 
& 4CGVSWHVK vent kits.

The  Corr/Guard  4CGSWHVK  &  4CGVSWHVK  vent  kits  are 
designed  for  sidewall  venting  of  instantaneous  tankless  water 
heaters  and  wall  hung  boilers.  Each  kit  contains  the  parts 
necessary to vent through any combustible wall. The vent kit is 
compatible with standard Corr/Guard products.

Be sure to read these instructions completely, and those of the 
appliance  itself,  before  proceeding  with  the  installation  of  this 
kit.  Additional  information  and  requirements  regarding  the  use 
and  installation  of  Corr/Guard  products  can  be  found  in  the 
installation instructions (L2153 and L2154). Installation is to be in 
accordance with local and national building codes.

The UL Listing for this product is void if components other than 
those  supplied  as  Listed  Components  by  Metal-Fab,  Inc.  are 
used. All  warranties,  stated  or  implied,  are  void  if  this  product 
and  the  appliance  to  which  it  is  connected  are  not  installed  in 
accordance  with  their  respective  instructions  and  jurisdictional 
code requirements.

Proper joint assembly is essential for a safe installation. Failure 
to follow these instructions and sound installation practices can 

lead to risk of damage, fire and carbon monoxide poisoning. 

KIT COMPONENTS:

The following items are included in the box for this kit:

 

 

• 

Wall thimble termination. 

 

• 

2 each male adjustable collars. 

 

• 

Telescoping 90-degree elbow. 

 

• 

Appliance adapter. 

 

• 

Installation instructions.

GENERAL REQUIREMENTS:

WARNING

: Failure to conform to any of these requirements. May 

violate local, state, or national codes and create conditions that 
may cause catastrophic property damage or personal injury.

• 

Proper operation of the vent system and appliance depends 

on  the  use  and  correct  assembly  of  all  parts  specified  by 

Metal-Fab, Inc. for a particular installation.

• 

If  required  by  the  appliance  manufacturer,  a  drain  fitting 

must be located as close as possible to the appliance flue 

outlet.

• 

More than one appliance may not be connected to the same 
vent kit termination.

• 

Vent  system  must  avoid  any  contact  with  plumbing  or 
electrical systems.

• 

Proper clearances to combustibles must be maintained over 
the entire length of the system (

FIG. 1

). Maximum appliance 

outlet temperature must not exceed 480 degrees Fahrenheit 

and a rating for positive pressure of 10” W.C..

• 

Refer to the appliances instructions to determine limitations 

with respect to the installation and use such as maximum 

horizontal  length  from  the  appliance,  maximum  height, 

joining  of  two  or  more  parts  to  constitute  the  intended 

assembly, maximum number of joints or sections of pipe for 

use in the assembly, and required installation clearances.

• 

Do not place any type of insulation in the required clearance 
spaces surrounding the vent system.

• 

Never install Corr/Guard on an appliance that is not listed for 
use with a Special Gas Vent or Type BH Vent.

• 

Additional  Corr/Guard  vent  lengths  can  be  installed 

for  extended  runs.  The  overall  equivalent  length  of  the 

system shall not exceed the specifications of the appliance 

manufacturer’s instructions.

• 

Horizontal vent runs shall have a slope of no less than 1/4 
inch (6.4mm) every 12 inches (305mm) to prevent collection 
of condensate.

• 

The  termination  should  be  away  from  trees,  shrubs,  or 

decorative items as flue gases could cause damage.

• 

The venting system must be free to expand and contract.

• 

Check  for  unrestricted  vent  movement  through  walls, 
ceilings, and roof penetrations.

• 

Manufacturers  have  different  joint  systems  and  adhesives. 

Do not mix pipe, fittings, or joining methods from different 

manufacturers. 

FIG. 1

3.00"

MIN.

1.00"

MIN.

APPLIANCE

WALL

ROOF

12.5"-16.0"

4.5"-9.0"

8.5"-12.0"

FIG. 1