background image

EXTERIOR INSTALLATION

1. 

Although it is not 

 

preferred practice, there 

  may be installations where
  Corr/Guard single wall vent 
 systems run vertically - 
  exterior to the building and a
  wall support(s) is needed.  A 
  wall support is used to secure 
  the vent system to a wall 
 

while maintaining the 

 

minimum clearance to 

  combustible construction.  
2. 

Wall supports must be 

  securely fastened to a solid 
  member of the building using 
  appropriate fasteners for
 various building materials 
  such as wood, steel siding or 
 masonry.
3. 

Wall supports located 

  exteriorly are to be vertically 
  spaced no more than 6 feet 
  (1.8 m) apart. 
4. Wall supports are designed 
  to be fastened to the vent by 
  means of clamping externally 
  to the vent. No screws are to 
  puncture the vent wall.

WARNING: Do not rivet or 
screw supports to the vent or 
otherwise puncture the vent 
wall.  

WARNING: Do not place any type of Insulation in any required clearance 
spaces surrounding the vent system.

MAINTENANCE

The Corr/Guard vent system should be inspected at least annually for the 
presence of deposits or debris and any accumulation should be removed.  The 
vent system should also be inspected at regular periods for signs of leakage of 
condensate or combustible products at any joint.

If the vent system incorporates a drain hose from either an inline fitting or from a 

drain tee, the hose must be inspected periodically to assure that water is in the 
trap loop.  If a proper trap loop in not maintained, exhaust from the connected 
appliances may accumulate in the building area.

IMPORTANT: The listing for this product is void if components other than 
those supplied as Listed Components by Metal-Fab, Inc. are used.  All 
warranties, stated or implied, are void if this product and the appliances to 
which it is connected are not installed in accordance with their respective 
instructions and local code requirements.

TO APPLIANCE

TO TERMINATION

INSIDE BUILDING 
SURFACE

OUTSIDE BUILDING

SURFACE

WOOD STUD

2" MIN. 

OVERLAP

Wall Thimble
Installation

1. Prior to installation, determine proper location of wall thimble so that a 

 

  minimum slope of 1/4” per foot is maintained in the horizontal section of vent 

  to ensure proper flow of condensation.

2. Prepare the wall by cutting a square opening 5

 larger than size of the vent 

  diameter.   (Opening size adequate to insert Wall Thimble components)

3. Install the Wall Thimble by inserting the larger of the two parts on the 
  appliance (interior) side.  
4. Next, apply a bead of sealant around the edges of the exterior (smaller of the 
  two parts) Wall Thimble component.  Then install this part of the Wall
  Thimble by inserting the smaller collar into the other component from the 
  previous step.

NOTE: The two horizontal cylinders of the Thimble must engage a mini-
mum of two inches.

5. Fasten both sides of the Wall Thimble using screws or nails.
6. Once the Thimble is installed, Corr/Guard vent pipe can be inserted into the 

  Thimble by inserting the male end first. (See figure above).  

7. Assemble Corr/Guard vent from the Wall Thimble section back to the 
 appliance.
8. Install a horizontal termination to complete the assembly.
9. Once assembly is completed, apply a bead of high-temp sealant around the 
  pipe and the exterior plate of the Thimble to protect against weather.

WARNING! Appliance outlet temperature shall not exceed 480

°

F (249

°

C) for 

venting systems that penetrate walls constructed of combustible materials.

VERTICAL VENTING

• 

Enclose residential exterior vent systems below the roof line or use double 

wall Corr/Guard (CG or CGV) to limit condensation due to cool down of flue 

gases.

• 

Unless installed in a fire rated shaft, a fire stop / vertical support is required

 

  when penetrating floors and ceilings.  

• 

Vertical supports are to be used after each transition to vertical. The

  maximum distance between vertical support plates is 30 feet (9.1 m).

• 

When assembling Corr/Guard vent, always align “UP” arrow away from the

 appliance. 

• 

The total equivalent length from the appliance outlet to the termination shall

  not exceed that length specified by the appliance manufacturer’s installation

 

 instructions.

• 

Vertical terminations must terminate no less than 2’  (0.61 m) above the

  roof or any wall or vertical structure closer than 8’ (2.4 m).  A vent cap or
  other equivalent termination is required to keep rain or debris out of the 
 vent.

1. Starting  at  the  appliance  outlet,  attach  the  first  section  or  appliance

 

 adaptor.
2. Continue assembly of pipe until nearing a ceiling penetration.  Locate and 

  cut hole in floor and ceilings that will be penetrated.  Hole size must maintain

 

  minimum listed clearances for single wall Corr/Guard (CGSW or CGVSW).

3. Install a firestop support when penetrating the ceiling to support the vertical

 

  run of the vent system.

4. When  installing  a  firestop  in  the

 

  attic,  the  firestop  or  support

 

  plate is located on top of the joist 
  to prevent insulation from falling 
  into the joist.  
5. 

Continue with the vent 

  penetrating the roof.  At the 
  roof, the opening must maintain 
  a minimum of clearance to 

  combustibles as specified

  in these instructions and on he 
  labeled vent product. 
6.

 

Above  the  roof,  a  flashing  and

 

  storm collar are required.  Use
  high temperature sealant to seal 
  the storm collar to the vent so 
  that rain will not penetrate the 
  roof opening.

 

PITCHED

FLASHING

STORM COLLAR

RAINCAP

SEE CHART FOR 

CLEARANCES

HIGH

TEMPERATURE
SEALANT

Roof Installation

APPLIANCE

APPLIANCE ADAPTOR

SEAL AT APPLIANCE 

WITH HIGH TEMP. RTV

TO DRAIN 

DISPOSE OF 

CONDENSATES

ACCORDING TO

 LOCAL CODES

HORIZONTAL 

DRAIN TEE OR 

DRAIN FITTING 

WITH TEE

HANGER STRAP

FIRESTOP

SUPPORT CLAMP

FIRESTOP

FLASHING

STORM COLLAR

RAINCAP

10'

 SEE NOTE 2

3' MIN.

NOTE 1 - APPLY CAULKING OR 

METAL-FAB MST TAPE WHERE 

VENT PASSES THROUGH STORM 

COLLAR.

NOTE 2 - 3' MINIMUM HEIGHT 

ABOVE ANY ROOF SURFACE 

WITHIN 10' HORIZONTALLY.

Vertical Installation

Rated Operating 

Temperatures

Minimum Clearance

Enclosed

Clearance

Unenclosed

Hor.

Vert.

Hor.

Vert.

3” & 4”

Diameter

400°F

(204°C)

8”

(203mm)

4”

(102mm)

1”

(25mm)

1”

(25mm)

480°F

(249°C)

8”

(203mm)

4”

(102mm)

2”

(51mm)

2”

(51mm)

550°F

(287°C)

N/A

N/A

2”

(51mm)

2”

(51mm)

5”

Diameter

400°F

(204°C)

N/A

6” 

(152mm)

1”

(25mm)

1”

(25mm)

480°F

(249°C)

N/A

6” 

(152mm)

2”

(51mm)

2”

(51mm)

550°F

(287°C)

N/A

N/A

2”

(51mm)

2”

(51mm)

C

US

LISTED

©2016 Metal-Fab, Inc. 

Form No.  L2153  -   5/16

         9537

Reviews: