background image

6

VARIABLE LENGTH

For  installations  that  require  non-standard  vent  lengths,  Corr/Guard 
Variable Length vent sections may be used. The vent section consists of 
an inner conduit that slip fits into the outer conduit, a compression band, 
or integral clamp and an outer casing for double wall only. 

3”- 5” (76mm-127mm) CG & CGSW

To  install  the  VL  vent  section,  first  install  the  inner  pipe  section  by 

connecting the male section to the adjoining double or single wall vent 

pipe. Insert male section until the bead of the joint stops at the edge of 

the female end of the vent section.
Next,  expand  the  length  of  the  inner  pipe  to  the  necessary  length  and 
tighten the integral clamping band  using a hex drive or screw driver. The 

VL’s are adjustable from 7 1/2” to 22” (191mm to 559mm). Continue with 

the next section of vent, making sure  to fully join the inner pipe of the 

vent from the female end of the VL vent.
When installing double wall, finish the VL vent assembly by installing the 
outer  casing  wall  around  the  VL  inner  pipe  section.  Secure  the  casing 

by installing #8x1/2” sheet metal screws at prepunched holes (See 

FIG. 

14

).

FIG. 15

WARNING:    Variable  Length  sections  are  not  intended  to  be 
subjected  to  vertical  force  loads.  Use  appropriate  support 
methods.

Supplementary  support  is  required  when  installing  offsets,  elbows  and 
non-vertical runs to prevent unacceptable stresses. Do not allow vent to 
sag or deflect from intended flow line during installation. 

WARNING:    Do  not  place  any  type  of  insulation  in  any  required 
clearance spaces surrounding this Vent System.

CONDENSATE DRAINS

If an appliance does not supply a condensate drain and one is required 
per  the  appliance  manufacturer’s  instructions  or  local  codes,  install  a 
drain  fitting  in  the  horizontal  conduit,  as  close  as  possible  to  the  appli-
ance vent collar.  

WARNING:  NEVER  INSTALL  A  DRAIN  IN  A  SYSTEM  WITH  AN 
APPLIANCE NOT INVESTIGATED FOR USE WITH A CONDENSATE 
DRAIN.

Corr/Guard drain fittings contain a 1/2” (

13mm

) diameter drain tube that 

should be located at the bottom of the vent or fitting when installed prop-
erly. A drain hose must be attached to the tube and a trap loop must be 
formed into the drain hose. The trap loop should be at least four times the 
appliance’s rated stack pressure in inches of water column or 6 inches 
(

153mm

), whichever is less. (See 

FIG. 16

)

When the Corr/Guard vent system is installed the system must be pres-

sure checked to for tightness. Repair any joint leaks by disassembling 

and  resealing  following  the  guidelines  in  the  Joint  Assembly  section  of 
these instructions. Replace any defective component.

The  Corr/Guard  ventilation  system,  manufactured  by  Metal-Fab,  Inc.. 
is constructed to exacting standards. The proper operation of this vent 
system  is  dependent  on  the  use  of  correct  components,  proper  sizing, 
quality  of  installation,  and  guidelines  and  limitations  expressed  by  the 
appliance manufacturer. 

TUBING

TRAP LooP
(4x STACK PRESSURE)

FIG. 16

6”- 24” (152mm-610mm) CG & CGSW

To install the VL, first apply a heavy bead of P077 Sealant into the inner 
vent  groove.  Then  slide  the  inner  vent  into  the  outer  vent.  Locate  into 

position and adjust to proper length. Follow Joint Assembly Details on 

PAGES  2  &  3

. Apply a bead of P077 Sealant at the joint of inner and 

outer vent and attach compression band. The 6” VL is adjustable from 

7½” to 10” (191mm to 254mm) and the 12” (305mm) VL is adjustable 

from 13½” to 22” (343mm to 559mm). When installing double wall, cut 

outer jacket to fit between the mating vent and install using sheet metal 

screws (supplied) (See 

FIG 15

).

INNER FLUE

CASING JACKET

INTEGRAL CLAMP

FIG. 14

COMPRESSION

BAND

OUTER

JACKET

FOR CG

ONLY

GROOVE

OUTER CONDUIT

INNER CONDUIT

SMALL DIAMETER CGSW & CG TO CGSW & CG

Connections  between  vent  and  fittings  are  male  /  female  type,  sealed 
with silicone sealant and secured with a profiled closure band. (See 

FIG. 

17

Connection Tips:

1.  Clean  male  and  female  joint  ends  to  remove  oil  and

 

 

contaminants  with  alcohol  pads  provided.  Apply  a  ¼  inch  

 

(

6.4mm

bead 

of 

sealant 

to 

the 

male 

connection  

 

approximately  ¼  inch  (

6.4mm

)  below  the  edge.  Also  apply  ¼  

 

inch  (

6.4mm

)  bead  of  sealant  (approx.  2  inches  long)  along  

 

the male joint at the overlap of the welded seam.

2. 

Insert  male  end  into  female,  twisting  slightly,  to  ensure  

 

even  distribution  of  sealant.  Be  sure  sections  are  seated. 

 

Inspect  the  joint  to  ensure  that  vent  gases  will  not  escape.

 

 

If  necessary,  apply  additional  sealant  to  any  visible  voids 

 

around the joint and smooth it into crevices.

3.  Align  profiled  closure  band  snugly  around  the  joint  section.

 

 

Insert  tongue  into  gear  clamp  and  tighten  with  3/8-inch  hex 

 

drive socket.  

IMPORTANT:  Profiled Vent connection band is formed to fit exactly 
over the joint section. This part is not symmetrical and should be 
installed  in  the  proper  orientation  for  maximum  seal  and  support. 
Allow sealant to cure for a minimum 24 hours before operating the 
appliance. Any adhesives used in the assembly of the system are to 
be used within their marked time limitations.

4.  For  CG  (double  wall)  joint  installations,  first  complete  steps

 

 

1 thru 3 as shown above. 

5.  Once  the  inner  vent  joint  has  been  connected,  locate  the

 

 

casing 

band 

around 

the 

casing, 

positioning 

the 

band 

 

between the formed beads on either casing.

6. 

Tighten  the  band  snugly  around  the  vent  casings  using  

 

3/8-inch hex drive socket.

Summary of Contents for CORR/GUARD

Page 1: ...ULLY EXAMINE ALL COMPONENTS FOR POSSIBLE SHIPPING DAMAGE BEFORE INSTALLATION PROPER JOINT ASSEMBLY IS ESSENTIAL FOR A SAFE INSTALLATION FOLLOW THESE INSTRUCTIONS EXACTLY AS WRIT TEN CHECK SEVERENESS O...

Page 2: ...may not be connected into the same vent system unless the appliance manufacturer specifically approved such a system and the appliances are designed for multiple venting Cat II III or IV appliances M...

Page 3: ...over the joint section This part is not symmetrical and should be installed in the proper orientation for maximum seal and support Allow sealant to cure for a minimum 24 hours before operating the app...

Page 4: ...ial exterior vent systems below the roof line or use double wall Corr Guard CG to limit condensation due to cool down of flue gases Unless installed in a fire rated shaft a fire stop vertical support...

Page 5: ...WN CAP DETAIL FIG 12 6 24 CG CGSW CAP CLoSURE RING SToRM CoLLAR FLASHING FOR CLEARANCE TO COMBUSTIBLES SEE TABLE 1 5 1 5M MAX UNLESS SUPPORTED BY GUY WIRES PLATE SUPPoRT USED AT RooF SEE CAP DETAIL PI...

Page 6: ...hese instructions Replace any defective component The Corr Guard ventilation system manufactured by Metal Fab Inc is constructed to exacting standards The proper operation of this vent system is depen...

Page 7: ...p is not maintained exhaust from the connected appliances may accumulate in the building area Where the duct is installed outside the building the aluminized steel outer casing must be primed and pain...

Page 8: ...8 P O Box 1138 WICHITA KANSAS 67201 316 943 2351 fax 316 943 2717 2008 Metal Fab Inc Form No L1704 10 08 8367...

Reviews: