 SERVICE SETTINGS 

14.1

 

BURNER 

Burner settings 

Firing up 

 

  Ignition test time 

Time  of  checking  whether  the  burner  is  ignited.  The  regulator  checks  if 
there  was  a  proper  rise  (increase)  of  exhaust  temperature.  After 
successfully completing the check, the regulator switches to OPERATION 
mode. 

  Feed time 

Fuel dosage feed time at ignition. 

  Ignition end exhaust temp. 

Exhaust temperature above which the burner is considered to be ignited. 
Ignition  test  is  ignored.  Note:  setting  a  low  temperature  may  result  in 
switching to OPERATION mode without a sufficient flame in the furnace. 
Recommended value: 130-

150 °C. 

  Exhaust delta 

Rise  (increase)  of  exhaust  temperature  necessary  to  switch  to 
OPERATION mode. 

  Ignition fan 

Fan  %  at  ignition.  Note:  setting  a  high  value  will  prolong  the  ignition 
process and result in failed ignition attempt. 

  Ignition time 

Time  of  consecutive  ignition  attempts.  After  this  time,  the  regulator  will 
make another ignition attempt (max. 3 attempts). 

  Fan time extension 

Between each ignition attempt, the fan works without the heater. Thanks 
to this, before making another ignition attempt, the possible flame in the 
burner has a chance to increase the exhaust temperature and cause the 
switch  from  IGNITION  to  OPERATION  mode  without  the  need  for 
additional ignition attempts.  

  Heating-up time 

Igniter heating-up time before switching on the fan. 

This should not be 

set  too  high  to  prevent  damage  to  the  heater.

  After  such  time,  the 

heater continues to work until an increase in the exhaust temperature is 
detected. 

Operation 

 

  OPERATION mode cycle time 

Complete cycle time of fuel feeding in OPERATION mode. 

OPERATION 

cycle time = OPERATION feed time 

+ feeder standstill time 

  Feeder efficiency 

Efficiency of the fuel feeder in kg/h. Entered a measured amount of fuel in 
constant feed (feeder working constantly). The parameter does not affect 
the work of the burner and is used for calculating the fuel level and current 
boiler output. 

  Fuel caloric value 

Fuel caloric value in Kwh/kg. This parameter is only used for information. 
The  parameter  does  not  affect  the  work  of  the  burner  and  is  used  for 
calculating the fuel level and current boiler output. 

  Container capacity 

Fuel container capacity used for calculating the fuel level.   Entering the 
correct  value  relieves  the  user  from  the need  to  calibrate  the  fuel level. 
The regulator uses this data if the fuel level has not been calibrated. After 
calibrating  the  fuel  level  successfully,  the  regulator  does  not  use  this 
parameter. 

  Feeder 

It is possible to conduct a feeder efficiency test and to set the duration of 
this test. Additionally, fuel weight can be entered here. This data facilitates 
the adjustment of fuel oriented parameters. 

Burning off 

BURNING OFF mode is not used when coal is the fuel of choice. 

  Burning off time 

Fan time in order to burn off remaining fuel.  

  Purge speed 

Fan speed during burning off in %.  

Supervision 

 

  Supervision time 

BURNING OFF mode and then into PAUSE mode. When the parameter 

Supervision  time  =  0

,  then  the  controller  skip  the  SUPERVISION  mode 

and  goes  directly  to  BURNING  OFF  mode.  When  the  parameter 

Supervision time = 255

then the controller stays in SUPERVISION mode

 

until  the  boiler  temperature  drops  down  up  to  the  level,  by  which  the 
controller returns to OPARATION mode. 

  Fan speed 

Fan speed in SUPERVISION mode; too high value may cause the boiler 
to overheat or the flame to return to the feeder; too low value results in 
fuel over-filling. 

Summary of Contents for ecoMAX 860P

Page 1: ...room panel ecoSTER200 and internet module ecoNET300 are not part of standard equipment regulator USER MANUAL AND INSTALLATION ISSUE 1 1 APPLIES TO SOFTWARE MODULE PANEL v 01 XX XX v 01 XX XX 02 2017 e...

Page 2: ...ed to water PRINCIPLES INDIVIDUAL FUZZY LOGIC The regulator must be programmed individually for the given type of boiler and fuel It is inadmissible to change the type of gear motor fan and to make ot...

Page 3: ...WEATHER SENSORS CONNECTION 26 12 8 CONNECTING EXHAUST SENSOR 26 12 9 CHECKING TEMPERATURE SENSORS 27 12 10 CONNECTION OF BOILER ROOM THERMOSTAT 27 12 11 CONNECTION OF MIXER S ROOM THERMOSTAT 28 12 12...

Page 4: ...for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boiler type is proper and whether it can cause danger The regulator...

Page 5: ...al is a supplement for the boiler manual In particular except for this manual the boiler manual should also be observed The regulator manual is divided into two parts for user and fitter Yet both part...

Page 6: ......

Page 7: ...INSTRUCTION MANUAL ecoMAX 860P...

Page 8: ...dule Night time decrease boiler On No Yes Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Night time decre...

Page 9: ...increase from mixer circulation increasing preset temperature for loading buffer warning HUW disinfection mode is active 4 way valve partially closed active return protection 5 fan operation symbol 6...

Page 10: ...itionally adjusted with individual fuel feeding times and fan speeds affecting the actual output of the boiler The output level parameters are accessible through the menu Boiler Settings Output modula...

Page 11: ...HUW container parameter Off set HUW priority using the Priority parameter in this case the CH pump is deactivated to speed up filling of the HUW container set simultaneous operation of the CH and HUW...

Page 12: ...a room thermostat which will equalize the inaccuracy of selecting heating curve if the selected heating curve value is too high In such case it is necessary to set the value of preset mixer temperatu...

Page 13: ...e selected heating curve value is too high if the outdoor temperature drops and the room temperature drops as well the selected heating curve value is too low if during frosty weather the room tempera...

Page 14: ...el is burned off In order to change modes turn the regulator off and on by clicking Work mode in the Current information tab 8 19 Manual control Regulator offers possibility to manual start of working...

Page 15: ...f done properly will set the parameters Feeder efficiency and Tank capacity which can be found in Service Settings Boiler settings 8 21 Information Information menu allows to preview temperatures bein...

Page 16: ...16...

Page 17: ...17 INSTALLATION AND SERVICE SETTINGS ecoMAX 860P...

Page 18: ...re set a high set temperature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid unn...

Page 19: ...temperature 55 C menu Service settings CH and HUW settings CH pump boiler pump YES menu Service settings CH and HUW settings Mixer 1 support CH activated menu Service settings Mixer 1 control Max pres...

Page 20: ...ings Buffer settings Loading start temperature 50 C menu Service settings Buffer settings Loading stop temperature 75 C menu Service settings Buffer settings Mixer 1 support CH activated menu Service...

Page 21: ...he controller in proximity of explosive gases or dust Moreover the controller cannot be used in conditions of water steam condensation or be exposed to effects of water 12 2 Mounting requirements Regu...

Page 22: ...e terminals and the leads Connection cables should not have contact with surfaces which temperature exceeds cables nominal operating temperature Terminals 1 22 are designed to connect devices supplied...

Page 23: ...the lead from the connector it is not allowed to coil excess of the cable and to leave not connected leads inside the casing of the regulator 1 cable outlets 2 holdfasts placing should be broken out...

Page 24: ...pper buffer temp sensor type CT4 BL lower buffer temp sensor type CT4 WS weather temp sensor type CT6 P FT exhaust temp sensor type CTS2 TR universal boiler thermostat NO NC H output to control the si...

Page 25: ...l sensor used with the BU feeder RM3 mixer 3 room thermostat RM4 mixer 4 room thermostat H2 voltage output for controlling the reserve boiler or alarm signalling or HUW circulation pump RELAY relay L...

Page 26: ...ensors and hot parts of the boiler and the heating installation Wires of sensors are resistant to temperature not exceeding 100 C 12 7 Weather sensors connection The regulator cooperates solely with t...

Page 27: ...74 2 CT2S PT1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 12 10 Conne...

Page 28: ...serve boiler gas or oil eliminating the necessity of enabling or disabling this boiler manually The reserve boiler will be enabled if the temperature of the pellet boiler drops and disabled when the p...

Page 29: ...iler circuit pipes Use pipes of large cross section for gravitational boiler circuit Electric diagram for switching valve of the reserve boiler where 1 regulator 2 reserve boiler 3 4 relay RM 84 2012...

Page 30: ...umentation of valve manufacturer and check whether the valve is properly connected calibrate factor of mixer valve opening To do this disconnect power supply of the regulator and set the selector on h...

Page 31: ...two wire connection power supply of 12V DC and rated current of min 200mA is required Disconnect GND and 12V wires from the module 2 and re connect them to external power supply unit arranged near eco...

Page 32: ...there should be written new software in the pfc format as a 2 files a file with the panel software and a file with the module A software Software files should be placed directly on the memory card do...

Page 33: ...nly water and exhaust Exhaust temperature fan reduction Return protection 4 way return protection Return hysteresis Min return temperature Valve closing Min boiler temperature Max boiler temperature B...

Page 34: ...parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection delay Flame return alarm feed time Hall sensor control Min RP...

Page 35: ...ERATION cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg h Entered a measured amount of fuel in constant feed feeder working constantly The p...

Page 36: ...These times may be edited in a special menu accessible only to the manufacturer of the boiler 14 2 BOILER Boiler settings Grate Max ignition time When this time is exceeded ant the exhaust temperatur...

Page 37: ...the status of the thermostat are sent from the room panel Pump Off by thermostat Available options No the CH boiler pump is not switched off when the room thermostat is activated YES the CH boiler pu...

Page 38: ...nsion time value Circulation pump standstill time It is the time between periods of circulation pump operation and it is defined by the parameter circulation standstill time recommended setting is bet...

Page 39: ...sing the set temperature above the value given for this parameter _ when the Mixer support On then the mixer pump will shut down by max mixer temperature 5 C which protects the floor against destructi...

Page 40: ...SETUP Show advanced setup Available options YES shows hidden parameters which edition is not recommended NO hides hidden parameters 14 7 RESTORE DEFAULT SETTINGS Restore default settings Restoring th...

Page 41: ...function of protection against flame recession is inoperative if the feeder sensor is disconnected or damaged The function of protection against flame recession is inoperative if the regulator is not...

Page 42: ...the encoder TOUCH and PLAY knob or restarting the power supply 15 9 Boiler overheating STB open contact This alarm occurs after activation of independent safety thermostat that secures the boiler agai...

Page 43: ...d by scale deposit To do this these components are periodically every 167h switched on for few seconds In this way the pumps are protected from immobilization caused by scale deposits Therefore during...

Page 44: ...44...

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ...Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfachtg com pl...

Reviews: