background image

26 

 

12.6

 

Connection of temperature 
sensors 

The  regulator  is  compatible  only  with  CT4 
and  CT2S  sensors. The use of  other sensors 
is prohibited!. 
Wires  of  sensors  can  be  extended  by  wires 
with diameter no smaller than 0,5mm

2

. Total 

length  of  wires  in  each  sensor  should  not 
exceed 15m.   
The  boiler  temperature  sensor  should  be 
installed  in  a  thermostatic  pipe  installed  in  
the  boiler.  Temperature  sensor  of  hot  water 
silo should be installed in a thermostatic pipe 
welded  into  the  silo.  The  mixer  temperature 
sensor should be installed in a sleeve located 
in stream of running water in pipe, but also it 
can  be  installed  on  the  pipe,  on  condition 
that it is thermally isolated from the pipe. 

 

Mounting  temperature  sensor:  1  -  pipe,  2  – 
clamps,  3  -  thermal  insulation,  4  -    temperature 
sensor. 

 

Sensor  must  be  protected  from 
getting  loose  from  the  surfaces 
to which they are connected. 

Good  thermal  contact  should  be  maintained 
between  sensors  and  the  measured  surface. 
To  this  purpose  thermal  grease  should  be 
used. It is not acceptable to lubricate sensors 
with water or oil. Wires of sensors should be 
separated  from  network  electrical  wires.  In 
such  a  case  wrong  readings  of  temperature 
may  be  shown.  Minimum  length  between 
those  wires  should  be  10  cm.  It  is  not 
acceptable to allow for contact between wires 
of sensors and hot parts of the boiler and the  
heating  installation.  Wires  of  sensors  are 
resistant  to  temperature  not  exceeding 
100°C.  
 
 

12.7

 

Connecting weather sensor 

he  regulator  cooperates  solely  with  the 
weather  sensor  type  CT6-P.  The  sensor 
should be installed on the coolest wall of the 
building.  Usually  it  is  the  northern  wall, 
under  the  roof.  The  sensor  should  not  be 
exposed  to  direct  sunrays  and  rain.  The 
sensor should be installed at least 2 m above 
the  ground,  far  away  from  windows, 
chimneys and other sources of heat.  
To  make  the  connection  use  wire  with 
diameter  at  least  0,5mm2  up  to  25m  long. 
Polarization of wires is not essential. Second 
end should be connected to terminals of the 
regulator  or  properly  to  the  used  kind  of 
regulator. 
The  sensor  should  be  screw  to  the  wall. 
Access  to  assembly  holes  is  possible  after 
unscrewing the cover of the sensor. 

 

12.8

 

Connecting exhaust sensor 

The  exhaust  sensor  should  be  fitted  in  the 
boiler flue. The gap between the sensor and 
the flue should be sealed. The sensor should 
be  installed  by  a  qualified  fitter,  while 
observing  regulations  applicable  for  chimney 
systems.  The  emission  sensor  should  be 
connected  to  the  sensor  terminals  acc.  to 
The  emission  sensor  lead  cannot  touch  hot 
elements  of  the  boiler  and  the  flue,  the 
temperature  of  which  exceeds  350°C.  The 
emission  sensor  should  be  installed  in  such 
distance  from  the  boiler  at  which  it  is  not 
directly  exposed  to  flames,  and  where  the 
emission  temperature  does  not  exceed 
450°C. 

Summary of Contents for ecoMAX860P TOUCH

Page 1: ...AX920P1 T INSTRUCTION INSTALLATION AND OPERATING MANUAL ISSUE 1 0 APPLIES TO SOFTWARE MODULE A PANEL v01 XX XX v 01 XX XX ecoSTER TOUCH ecoNET300 functions available in the additional module B room pa...

Page 2: ......

Page 3: ...OF TEMPERATURE SENSORS 26 12 7 CONNECTING WEATHER SENSOR 26 12 8 CONNECTING EXHAUST SENSOR 26 12 9 CHECKING TEMPERATURE SENSORS 27 12 10 CONNECTION OF MIXERS ROOM THERMOSTAT 27 12 11 CONNECTION OF BOI...

Page 4: ...for boiler manufacturers Before applying the regulator a boiler manufacturer should check if the regulator s mating with the given boiler type is proper and whether it can cause danger The regulator...

Page 5: ...supplement for the boiler manual In particular except for this manual the boiler manual should also be observed The regulator manual is divided into two parts for user and fitter Yet both parts contai...

Page 6: ...6...

Page 7: ...INSTRUCTION MANUAL ecoMAX 860P TOUCH...

Page 8: ...libration Scheduled On Reduction value Schedule HUW settings HUW preset temperature HUW pump mode Off Priority No priority HUW container hysteresis HUW disinfection Schedule HUW On No Yes Reduction va...

Page 9: ...meaning of the symbols opening of room thermostat contacts preset room temperature has been reached of preset boiler temperature for active time intervals increase of preset boiler temperature for the...

Page 10: ...l After three unsuccessful attempts an alarm Failed firing up attempt is reported In such case the boiler operation is halted Boiler operation cannot be continued automatically service crew must inter...

Page 11: ...e boiler temperature decreases and the boiler automatically switches to OPERATION mode For the setting Supervision time 0 the regulator skips the SUPERVISION mode and enters the BURNING OFF mode When...

Page 12: ...function can be activated automatically with the Auto parameter including settings for SUMMER mode act temperature SUMMER mode deact temperature 8 15 Disinfection HUW container The regulator has a fun...

Page 13: ...ot recommended to use both options at the same time Automatic correction of room temperature is carried out in accordance with the following formula Correction Preset room temperature measured room te...

Page 14: ...r boiler heating circuits HUW container and circulation pump operation The intervals can be used to define time periods at which lower preset temperature may be set e g for a night time or when the us...

Page 15: ...tion No additional fuel level sensors are required Calibration To perform calibration fill the fuel tank to the level corresponding to its full load and set the parameter Boiler settings Fuel Level Fu...

Page 16: ...In Touch version in the menu bar at the bottom of the screen there is a button Upon activation of this key a quick selection menu appears To add new item to this menu hold respective icon pressed in...

Page 17: ...INSTALLATION AND SERVICE SETTINGS ecoMAX 860P TOUCH...

Page 18: ...ature of the boiler In order to improve the water circulation in natural systems highlighted circuit in the figure use large nominal diameter pipes and four way valve avoid unnecessary angles and redu...

Page 19: ...u Service settings CH and HUW settings CH pump boiler pump YES menu Service settings CH and HUW settings Mixer 1 support CH activated menu Service settings Mixer 1 control Max preset temp of mixer 1 7...

Page 20: ...Loading start temperature 50 C menu Service settings Buffer settings Loading stop temperature 75 C menu Service settings Buffer settings Mixer 1 support CH activated menu Service settings Mixer 1 sett...

Page 21: ...12 1 Environmental conditions Due to fire risk it is forbidden to use the controller in proximity of explosive gases or dust Moreover the controller cannot be used in conditions of water steam condens...

Page 22: ...in accordance with applicable regulations Caution After the regulator is turned off using the keyboard dangerous voltage can occur on the terminals Before starting any assembly works you must disconn...

Page 23: ...If there is a necessity to strip cable insulation more than 60mm cable leads should be fasten together or with other leads near the connector in order to prevent contact with unsafe parts in the case...

Page 24: ...pper buffer temp sensor type CT4 BL lower buffer temp sensor type CT4 WS weather temp sensor type CT6 P FT exhaust temp sensor type CTS2 TR universal boiler thermostat NO NC H output to control the si...

Page 25: ...l sensor used with the BU feeder RM3 mixer 3 room thermostat RM4 mixer 4 room thermostat H2 voltage output for controlling the reserve boiler or alarm signalling or HUW circulation pump RELAY relay L...

Page 26: ...f sensors and hot parts of the boiler and the heating installation Wires of sensors are resistant to temperature not exceeding 100 C 12 7 Connecting weather sensor he regulator cooperates solely with...

Page 27: ...1000 3 25 1096 9 1097 3 1097 7 50 1193 4 1194 0 1194 6 100 1384 2 1385 0 1385 8 125 1478 5 1479 4 1480 3 150 1572 0 1573 1 1574 2 CT2S PT1000 exhaust Temp C Min Nom Max 0 999 7 1000 0 1000 3 25 1096...

Page 28: ...e system caused by a pump stop The pump interlock by opening the contacts of the room thermostat may be activated only upon making sure the boiler will not be overheated 12 12 Connection of reserve bo...

Page 29: ...to ensure free gravitational flow of water in the boiler circuit active cross section of switching valve 4 has to be larger than or equal to cross section of boiler circuit pipes Use pipes of large c...

Page 30: ...supply check whether wires to mixer closing and opening are not interchanged To do this enter MENU Manual control and open the mixer by selecting Mix1 Open ON When opening the servo the temperature on...

Page 31: ...cross section area of the wire should not be less than 0 5 mm2 12 18 Software update Simultaneous update of the regulator and panel software can be done using memory card only type microSDHC Software...

Page 32: ...Lack of fuel detection method Exhaust only Water and exhaust Boiler hysteresis Purge operation supervision Purge interval supervision Return protection Return protection 4D Return hysteresis Min retu...

Page 33: ...o adequate sensor or additional module is connected or the parameter is hidden Manufacturer menu Reset counters Reset alarms Exhaust alarm temperature Flame return feed time Flame return detection del...

Page 34: ...cycle time OPERATION feed time feeder standstill time Feeder efficiency Efficiency of the fuel feeder in kg h Entered a measured amount of fuel in constant feed feeder working constantly The parameter...

Page 35: ...for exceeding the maximum feeder temperature is displayed When this temperature is exceeded the feeder is engaged for a predefined time with a several minute pause If the temperature drops the regula...

Page 36: ...e boiler Determines pellet boiler temperature below which reserve boiler is activated i e gas boiler Setting 0 value causes deactivation of reserve boiler control and switching joint number 43 44 on a...

Page 37: ...min The circulation pump is operating in cycles for the time of circulation operation time recommended setting is between 60 and 120s Circulation pump operation time CH pump working mode Available opt...

Page 38: ...g it should be set for the value below 45 50 C or even lower when the thermal resistance of this floor is lower Attention setting too lower value of this parameter can lead to unnecessary shut down of...

Page 39: ...r Alarms when an alarm occurs output 43 44 is activated Alarm exhaust temperature Exhaust temperature above which the alarm will be activated Available only in the GRATE mode Flame retract feeding tim...

Page 40: ...cancelled only after the feeder temperature decreases by restarting the regulator The function of protection against flame recession is inoperative if the feeder sensor is disconnected or damaged The...

Page 41: ...ss the Reset button 15 10 Max exhaust temperature exceeded Sensor damage danger This alarm occurs only when using the GRATE and exceeding the maximum exhaust temperature The fan is turned off Its aim...

Page 42: ...parameter can be found in Service settings Burner settings If the parameter Additional feeder operation time is set to 0 this work additional feeder is turns off 17 REPLACEMENT OF PARTS AND COMPONENT...

Page 43: ......

Page 44: ...19 Ignatki 16 001 Kleosin Poland phone 48 85 749 70 00 fax 48 85 749 70 14 plum plum pl www plumelectronics eu Jacek Kucharewicz ul Sikorskiego 66 16 100 Sok ka Poland tel 48 85 711 94 54 www metalfac...

Reviews: