10
@2019 KITA Sensor Tech. Co., LTD. URL hiip://www.kita.com.tw
-8-
Installation Instructions
K F P 0 1
Series
Instruction Manual
●
PNP Output / Analog Voltage Output / External Input
●
PNP Output / Analog Current Output / External Input
1
2
3
4
5
6
Brown (Power )
Brown (Power )
Blue (Power supply –)
Blue (Power supply –)
Black (Output 1)
White (Output 2)
Black (Output 1)
White (Output 2)
Yellow (External input)
Yellow
(External input)
Orange
(Analog output)
Orange
(Analog output)
1
2
3
4
5
6
1k
Ω
1.3 Wiring Diagrams
1.3.
1 PNP Output, Analog Output and External Input
Brown
Orange
Yellow
Black
White
Blue
Pin No. Line color
Content
1
Brown
Power supply (DC 12 to 24V DC)
4
Black
Output 1 (Max. load current
:
125mA)
5
White
Output 2 (Max. load current
:
125mA)
3
Yellow
External input
2
Orange
Analog voltage output
:
1
- 5V
Analog current output
:
4
- 20mA
6
Blue
0V (GND)
1
2
3
4
5
6
Main Circuit
Main Circuit
Load
Load
Load
Load
Load
Summary of Contents for FLUX 0
Page 1: ...FLUX 0 DIGITAL FLOWMETER AND PRESSURE SENSOR USER MANUAL...
Page 2: ...2...
Page 6: ...6...