3.3.6.3 Unit Parameters
Common parameters - General parameters temperature CHx-CHy I5F90...I5F93
• Unit of measurement - Temperature scale_I5F90_S01: temperature reading option °Celsius or °Fahrenheit.
I5F9x_S01 = 0 °Celsius
I5F9x_S01 = 1 °Fahrenheit
•
Noise suppression- NoiseRejection_I5F9x_S02
:
suppresses electrical noise generated by mains electricity supply.
This parameter works in conjunction with the "Acquisition Filter" parameter.
I5F9x_S02 = 0 50 Hz: suppresses noise generated by 50Hz mains electricity supply
I5F9x_S02 = 1 60 Hz: suppresses noise generated by 60Hz mains electricity supply
I5F9x_S02 = 2 50/60 Hz slow: suppresses noise generated by 50Hz and 60Hz mains electricity supply.
A high level of filtering is achieved, but with a delay in data acquisition.
I5F9x_S02 = 3 50/60 Hz fast: suppresses noise generated by 50Hz and 60Hz mains electricity supply.
Very fast acquisition is achieved, but with a low level of filtering.
Noise suppression
Sync 3
Sync 4
Noise attenuation (dB)
Data acquisition delay (ms)
Noise attenuation (dB)
Data acquisition delay (ms)
50 Hz
95
60
120
80
60 Hz
95
50
120
67
50/60 Hz Slow
100
300
120
400
50/60 Hz Fast
67
60
82
80
Specific parameters - Config parameters CHx Temperature_I5F94...I5FA3
• Type of sensor - SensorAdjustment_I5F9x_S01: possible choice of the type of sensor used among those available.
I5F9x_S01 = 0 No sensor connected
I5F9x_S01 = 1 Pt 100 (TK=0.00385)
I5F9x_S01 = 2 Pt 200 (TK=0.00385)
I5F9x_S01 = 3 Pt 500 (TK=0.00385)
I5F9x_S01 = 4 Pt 1000 (TK=0.00385)
I5F9x_S01 = 5 Pt 100 (TK=0.00391)
I5F9x_S01 = 6 Pt 200 (TK=0.00391)
I5F9x_S01 = 7 Pt 500 (TK=0.00391)
I5F9x_S01 = 8 Pt 1000 (TK=0.00391)
I5F9x_S01 = 9 Ni 120 (TK=0.00617)
I5F9x_S01 = 10 Ni 200 (TK=0.00617)
I5F9x_S01 = 11 Ni 500 (TK=0.00617)
I5F9x_S01 = 12 Ni 1000 (TK=0.00617)
I5F9x_S01 = 13 TC Type E
I5F9x_S01 = 14 TC Type J
I5F9x_S01 = 15 TC Type T
I5F9x_S01 = 16 TC Type K
I5F9x_S01 = 17 TC Type N
I5F9x_S01 = 18 TC Type S
I5F9x_S01 = 19 TC Type B
I5F9x_S01 = 20 TC Type R
• Type of connection (for RTD only) - ConnectionTechnology_I5F9x_S02: possible choice of the type of sensor connection, if with 2, 3 or 4
wires.
I5F9x_S02 = 0 2 wires
I5F9x_S02 = 1 3 wires
I5F9x_S02 = 2 4 wires
• Cold joint compensation (for TC only) - ColdJunctionCompensation_I5F9x_S03: possible choice of an external cold joint instead of the one
already installed internally.
The external cold joint (Pt1000) is recommended in case of sudden changes in the ambient temperature.
I5F9x_S03 = 1 internal (default)
I5F9x_S03 = 0 external
• Measurement resolution - MeasureResolution_I5F9x_S04: possible choice of measurement resolution in tenths or hundredths of °C.
The resolution in hundredths only applies to RTD sensors, with temperature reading of m/- 327°C.
I5F9x_S04 = 0 0.1
I5F9x_S04 = 1 0.01
• Sensor disconnected signalling - SignalingDisconnectedSensor_I5F9x_S05: if enabled, the breakage of a wire generates an alarm.
I5F9x_S05 = 0 disabled
I5F9x_S05 = 1 enabled