• Short-circuit signalling (for RTD only) - Short_circuitSignaling_I5F9x_S06: if enabled, a short circuit of the sensor connection generates an
alarm.
I5F9x_S06 = 0 disabled
I5F9x_S06 = 1 enabled
• Minimum value monitor - MonitorLowestValue_I5F9x_S07: when this function is enabled, an alarm is generated when the temperature falls
below the set minimum value.
I5F9x_S07 = 0 disabled
I5F9x_S07 = 1 enabled
• Maximum value monitor - MonitorHighestValue_I5F9x_S08: when this function is enabled, an alarm is generated when the temperature is
above the set maximum value.
I5F9x_S08 = 0 disabled
I5F9x_S08 = 1 enabled
• Measured Value Filter - FilterMeasuredValue_I5F9x_S09: a mathematical filter that ensures a more stable temperature reading.
By setting a filter value on the sampling of the highest signal, improved reading stability is achieved but with a longer delay in data display.
I5F9x_S09 = 1 1 samples
I5F9x_S09 = 2 2 samples
I5F9x_S09 = 3 4 samples
I5F9x_S09 = 4 8 samples
I5F9x_S09 = 5 16 samples
I5F9x_S09 = 5 32 samples
I5F9x_S09 = 6 64 samples
• Minimum value - LowestValue_I5F9x_S0A
• Maximum value - HighestValue_I5F9x_S0B
• Acquisition filter - AcquisitionFilter_I5F9x_S0C: it defines the type of digital filter. It works in conjunction with the "Noise suppression"
parameter.
By setting the Sync 4 filter, a level of filtering higher than the one with the Sync 3 filter is achieved, but with a longer delay in data acquisition.
I5F9x_S0C = 0 Sync3
I5F9x_S0C = 1 Sync4