73
The diagnosis of the EB 80 POWERLINK system is defined by the state of the interface LED lights.
Each component in the system relays its state, locally by LED lights, and to the POWERLINK node by software messages.
9.1 POWERLINK NODE DIAGNOSTIC MODE
The diagnosis of the EB 80 POWERLINK system is defined by the state of the interface BS, BE, P1 and P2.
9. DIAGNOSTICS
Led
STATE
Meaning
P1/ P2
link/act
OFF
No connection to POWERLINK
ON
(green)
The device is connected to the network but there is no data exchange
GREEN
The device communicates with the network
(flashing)
BS
OFF
The device is in the INIT state
GREEN
(double flashing)
The device is in the PRE-OPERATIONAL state (2° state)
GREEN
(single flashing)
The device is in the PRE-OPERATIONAL state (1° state)
GREEN
The device is in the OPERATIONAL state
BE
OFF
No error - the device is working properly
ON
(red)
Configuration or communication error, cable disconnected
9.2 EB 80 SYSTEM DIAGNOSTIC MODE – ELECTRICAL CONNECTION
Diagnosis of the EB 80 system - Electrical Connection - is defined by the state of Power, Bus Error and Local Error LED lights.
Diagnostic functions of the EB 80 system relay the state of the system via error codes in hexadecimal or binary format to the controller, in order of
priority. The state byte is interpreted by the controller as an input byte.
The table below shows the correct interpretation of the codes.
LED light state
Hex code
Meaning
Notes
Solution
Power
Bus Error
Local Error
ON
(green)
OFF
ON
(red)
0xFF
System limits exceeded,
comunication line data
overflow
Number of I/Os to be checked
simultaneously is too high or
the control frequency is too
high.
Modify the system by reducing the
number of I/Os to be checked
simultaneously.
Contact technical support
ON
(green)
OFF
ON
(red)
0xD4 ÷ 0xD7
fault with a temperature
analogue input module
• Sensor not connected
• Wrong parameters
Check the connection and the
parameters set
ON
(green)
OFF
ON
(red)
0xD0 ÷ 0xD3
Analogue input module not
calibrated
-
Contact technical support
ON
(green)
OFF
ON
(red)
0xCC ÷ 0xCF
Fault with analogue output
or total module current
too high
Individual output fault/
module over-demand/
DAC errors
Turn off power supply and remove the
cause of failure
ON
(green)
OFF
ON
(red)
0xC8 ÷ 0xCB
Fault with analogue input
or total module current
too high
Under-overflow out of range
single input / over-absorption
of the module
Turn off power supply and remove the
cause of failure
ON
(green)
OFF
ON
(red)
0xB0 ÷ 0xC5
Digital output failure or total
current of module too high
Short-circuit of an individual
output / module overcurrent
Turn off power supply and remove the
cause of failure
ON
(green)
OFF
OFF
0xA0 ÷ 0xAF
Overcurrent of a digital input
Signalled by one input
Turn off power supply and remove the
cause of failure
ON
(green)
OFF
ON
(red)
0x20 ÷ 0x9F
Valve 1 / 128 faulty
**
Solenoid pilot short-circuited,
interrupted or not connected
Turn off power supply and remove the
cause of failure
GREEN
(flashing)
OFF
OFF
0x17
No auxiliary power
-
Insert auxiliary power supply
Summary of Contents for EB 80 ETHERNET POWERLINK