18 Conventional Products—DH400 Conventional Air Duct Smoke Detector
1.
Perform the Standby and Trouble Tests as described in the Testing
Standby, Alarm, and Sensitivity section of this technical bulletin.
2.
Perform the M02-04-00 Magnet Test as described in the Testing
Alarms section of this technical bulletin.
The RTS451 Remote Test Station Test as described in the Testing
Alarms section of this technical bulletin may substitute for this
requirement.
3.
Perform the Airflow Test as described in the Testing Smoke Entry
section of this technical bulletin.
4.
Perform the Smoke Response Test as described in the Testing Smoke
Entry section of this technical bulletin.
5.
Perform the MOD400 or MOD400R Test and R59-18-00
Calibrated Test Card Tests as described in the Testing Sensitivity
section of this technical bulletin.
6.
Record all test results in the Detector Test Log section of this
technical bulletin.
1.
Install the cover using the four screws that are fixed in the
housing cover.
2.
Be certain filters are installed as described in the Install the Filters
section of this technical bulletin.
3.
Make sure the cover fits into the base groove and all gaskets are in
their proper positions.
4.
Tighten the four cover screws to 10 in·lb.
Perform
Detector Check
Install the Cover