6 Conventional Products—DH400 Conventional Air Duct Smoke Detector
Table 3: Specifications Summary
Description
HVAC air duct mounted ionization or photoelectronic
smoke detector for 2-wire alarm systems
Environmental Limits
Temperature
32 to 120°F (0 to 49°C)
Humidity
10 to 93% Relative Humidity, Non-condensing
Air Velocity
300 to 4000 ft/min.
1.5 to 20.3 m/sec.
Test Features
Magnetic Test Switch
MOD400R Test Module
RTS451 Remote Test Station
R59-18-00 Calibrated Test Card
Mechanical
Length
14.5 in. (368.3 mm)
Width
5 in. (127 mm)
Depth (installed)
4 in. (101.6 mm)
Weight
3.5 lb (1600 g)
Terminals
Captive universal terminal screws with sems plates accept
wire sizes of 14 gauge or smaller. The screws will
withstand 10 in·lb of tightening torque without damage.
Accessories
M02-04-00
Replacement Test Magnet
RA400Z
Remote Annunciator Alarm LED
RTS451
Remote Test Station, Test Switch with Alarm, and
Power LEDs
CRT400
Detector Head Cover Removal Tool (Ion only)
F36-05-00
Replacement Air Filter (two per package)
MOD400R
Sensitivity Test Module
P48-21-00
Replacement End Plug for Inlet Sampling Tube
R59-18-00
Replacement Calibrated Test Card (for Photo Units Only)
RS14
Replacement Screen, Ionization Detector Head (1451DH)
RS24
Replacement Screen, Photoelectronic Detector Head
(2451)
A2650-01
Replacement Installation Kit (Mounting Hardware)
Sampling (Inlet) Tubes
Tube
Outside Duct Width
ST-1.5
1 to 2 ft (300 to 600 mm)
ST-3
2 to 4 ft (600 to 1200 mm)
ST-5
4 to 8 ft (1200 to 2400 mm)
ST-10
8 to 12 ft (2400 to 3700 mm)
Exhaust Tube Extension
A2440-00
5.75 in. (146 mm) additional
Continued on next page . . .