Conventional Products—DH400 Conventional Air Duct Smoke Detector 9
Installation Procedures
This section contains installation information for DH400 air duct smoke
detector. Instructions are given for mounting and wiring the detector, and
basic installation information is provided.
!
CAUTION: Personal injury hazard. This device will not
operate without electrical power. Frequently, fire
situations may cause an interruption of power. The
system safeguards should be discussed with your local
fire protection specialist.
This device will not sense smoke unless the ventilation system is
operating. This detector housing is not a weatherproof device; therefore, it
should not be installed above the building roof line and must be protected
from the elements.
1.
Verify duct airflow direction and velocity.
2.
Drill the mounting holes.
3.
Secure the detector housing to the duct.
4.
Install the sampling inlet tube.
5.
Complete the field wiring.
6.
Install the filters and check the pressure differential.
7.
Perform the detector check.
8.
Install the cover.
Model DH400 detectors are designed to be used in air handling systems
having air velocities of 300 to 4000 feet per minute. Be sure to check
engineering specifications to ensure that the air velocity in the duct falls
within these parameters. If necessary, an Alnor Model 6000-P velocity
meter or equivalent, may be used to check the air velocity in the duct.
General
Information
Installation
Installation
Sequence
Verify Duct
Airflow Direction
and Velocity