Installation Manual
MX15 Series
14
2 X DISTANCE X CABLE RESISTANCE PER FT. X CURRENT = VOLT DROP
Table 2-2: Suggested Output Wiring Sizes
Load Current
Wire Gauge (US)
Circular Mils
(kcmils)
Metric (mm2)
65 AMPS
6 AWG
26.24
13.3
130 AMPS
4 AWG
41.74
21.1
2.6.2 Output Terminal Blocks
The MX15-1 and the MX15-1Pi have one output terminal block. The terminal block is large
enough to accommodate the recommended wire gauge sizes shown in Table 2-2. The terminal
block is located in the lower left corner on the rear of the unit. The rear panel needs to be
removed to access this terminal block.
CAUTION: REMOVE ALL INPUT POWER TO THE MX15 BEFORE
REMOVING THE REAR PANEL.
The correct standard size Allen wrench for connecting output wiring to TB1 is supplied with each
MX15 in the ship kit. Look for a brown envelope. If the correct tools cannot be found, contact
California Instruments customer service at
support@calinst.com
.
Terminal 2 of TB1 provides the output LO connection, and terminal 1 of TB1 provides the output
HI connection. The location of TB1 is shown in Figure 2-2.