15
A01-00055 Rev M
UPM Load and Battery Indicators
UPM display showing normal operation
(Fully charged batteries with 60% load shown)
UPM display showing in battery backup operation
(Batteries 80% charged with 60% load shown)
UPM display showing an overload condition (Batteries
100% charged and greater than 100% load shown)
UPM display showing over-temperature condition
(Batteries 80% charged with 80% load shown)
UPM display showing a bad battery condition
(Inspect or replace battery unit loaded to 60%)
NOTE:
Depending on the charge state of the battery, it is possible
that the battery charge level LEDs may be flashing (this is
normal).
Initial Startup
With the connected equipment powered off, perform an initial test of
the UPM backup function by pressing the Test/Silence button on the
front panel for 5 seconds. During this test, the Battery LED ( ) on the
front panel should briefly illuminate. It is also possible to test the backup
function by unplugging the UPM input power cord. If you choose to test
the UPM in this manner, you will note that the UPM will beep every few
seconds while the power cord is unplugged. The Battery LED ( ) will
also illuminate constantly.
Once you have performed an initial test of the UPM backup function,
turn on the connected computer equipment. Verify that the unit is not
overloaded. If the unit is overloaded all load LED’s will be on the fault
LED ( ) will flash, remove the least critical devices from the UPM one
by one until the overload LED is extinguished. With the connected loads
powered up, perform the backup test once again by pressing the Test/