22| 52
blue’Log X series
6.1.2
Device protection when wall-mounted
Voltage:
Current:
24 V DC
1.6 … 6.2 A
To limit the power consumption of the blue'Log a DC power supply with power limiter
and a maximum output current of 6.2 A has to be used
A suitable power supply can be found in the meteocontrol product portfolio:
a.
AC/DC Adapter HN-Power, type HNP 36EU-240
ATTENTION
power supply
Please exclusively use direct-current power supplies (DC) with safety extra
low voltage (SELV).
6.2
Voltage output
Voltage: 24 V DC
The integrated power supply can supply sensors (e.g. i'checker) with a maximum
current consumption of 500 mA. For sensor current consumptions totaling more than
500 mA, please use an external power supply.
6.3
Ethernet connection
Direct connection between the blue’Log and a PC / laptop or hub / switch via an
Ethernet patch cable. The cable is supplied with the device.
6.4
Analog input
The analog inputs are freely configurable as:
Voltage input: 24 V DC
Voltage input: 0-1 V DC
Voltage input: 0-100 mV
Current input: 0-20 mA
Resistor (PT1000): 600-1800
Ω
The four analog inputs are multi inputs either for analog or digital signals, to be
configured per port via software.