blue’Log X series
23| 52
6.5
Digital input
The digital inputs are freely configurable as:
Pulse input in accordance with DIN 43864 (S0)
Voltage level input: 0-24 V DC
Dry contact: 24 V DC / 20 mA
The four digital inputs are multi inputs either for analog or digital signals, to be
configured per port via software.
6.6
Digital output
The digital outputs are freely configurable as:
Open collector: Max. 60 V DC / 200 mA
Voltage output: 10-60 DC (corresponding to supply voltage), max. 200 mA
6.7
RS485/422 interface
Connects communication devices via the RS485 or the RS422 bus.
Each RS485/RS422 interface is automatically switched and can be terminated
individually.
Please note the respective requirements for connecting bus devices given in the
enclosed "blue’Log M and X series device connection plans" document.
6.8
CAN interface
Connects communication devices via the CAN bus.
The CAN interface can be terminated.
6.9
USB interface
USB front socket (type A) as a service interface suitable for firmware updates.