48| 52
blue’Log X series
Digital Inputs
4 x digital inputs (mode per port individually configurable via software)
The following options are available for each input:
Type
Usage
Range
Precision
Resolution
Digital
Potential-free contact
24 V DC / 20 mA
Digital
S0
S0- compliant
Digital Outputs / Multi Inputs
Each of the four ports has a pin for a digital output, a multi input and a ground:
4 x digital outputs (mode per port individually configurable via software)
4 x multi inputs (mode per port individually configurable via software)
The following options are available for each digital output:
Type
Usage
Range
Digital
Open Collector
Max. 60 V DC / 200 mA
Digital
Voltage output
10-60 V DC (corresponding to the supply
voltage), max. 200 mA
The following options are available for each multi input:
Type
Usage
Range
Precision
Resolution
Digital
Voltage level input
0-24 V DC
Digital
Potential-free contact
24 V DC /
20 mA
Digital
S0
S0- compliant
Analog
Voltage input
0-10 V DC
2 mV DC
40 µV DC
Analog
Voltage input
0-1 V DC
0,2 mV DC
4 µV DC
Analog
Voltage input
0-100 mV DC
20 µV DC
0,4 µV DC
Analog
Current input
0-20 mA
4 µA
100 nA
Analog
Resistor (PT1000)
600-1800
2
0,5
Memory
Service interface
Expandability
SD card slot
USB front socket (type A)
The system may be expanded with additional interfaces
by connecting further MX modules. Please note the
limitations stated under "Software features".