14| 52
blue’Log X series
5.2.3
Maximum recommended cable lengths
Bus cabeling (RS485 data cable)
Sensors (voltage signal 0 V – 10 V)
Sensors (current signal 4 mA – 20 mA)
Meters
Ethernet-network
1200 m
2) 3)
100 m
600 m
4)
10 m
100 m
3)
1)
We recommend using the cable type UNITRONIC
®
Li2YCYv (TP) manufactured by Lapp Kabel,
or an equivalent cable type. This cable is suitable for laying in soil.
2)
For longer cable lengths, repeaters are required.
3)
Several separate lengths of cable require a hub.
4)
24 V DC power supply required.
Data cables must have to be isolated from power cables in accordance
with EN 50174-2 using metal cable trays.
Shielding
The cable shielding may only be grounded at one end of the connection.