blue’Log X series
101 | 120
14.4.10
Q(P
tan
φ
(fix)) procedure
In this procedure the reactive power Q is used as control value.
Here the reactive power is set according to the power fed in by recording the active
power P at the grid connection point by the selected measuring device and transferring
the measurements to the data logger. The logger assigns the control value Q to the
relevant power via tan
φ
–
tan
φ
is stipulated here.
Fig. 82: Q(P
tan
φ(
fix)) Power Control procedure: Specified reactive power curve
Input box
Meaning
tan
ϕ
Constant value for tan
ϕ
P
Limit
Lower active power(P) limit up to which the characteristic
curve is traveled before the corresponding value Q is
used as the fixed value. In %/P
AV
Excitation
Excitation of the specified control value (overexcited /
under-excited)
This procedure requires a power quality analyzer that has been
connected to the data logger and configured.