blue’Log X series
109 | 120
14.4.18
System control loop
With the help of the "System control loop" setting option, the relevant reactive power
procedure can be used for control purposes (open control loop; selection of control
loop
"OFF") or regulation purposes (closed control loop; selection of system control
loop
"ON"). Enabling a system control loop provides compensations for
inconsistencies between production and the grid connection point (GCP), which occur
due to the reactive power requirement of medium voltage cables and the transformer.
Fig. 85: Power Control reactive power procedure: Reactive power regulation
Input box
Meaning
System control loop
Enables reactive power regulation in a closed loop
Transformer
If enabled, the reactive power requirement of the
transformer is taken into account during regulation
Transformer nominal
power
Details of the transformer nominal power
Lower P
Limit
Active power threshold above which reactive power
regulation is enabled
Lower cos
φ
Limit
Operating limit for reactive power regulation for cos
φ
Upper Q
Limit
Details of the operating limit for reactive power regulation
for Q