24 | 120
blue’Log X series
6.2
Voltage output
Voltage: 24 V DC
The blue’Log can supply sensors (e.g. i'checker) with a maximum current consumption
of 500 mA. For sensors with a current consumption totaling more than 500 mA, please
use an external power supply.
6.3
Ethernet
The blue’Log is directly connected to the PC / laptop or hub / switch using an
Ethernet patch cable, which is included in delivery.
6.4
Multi input
The blue'Log has four multi inputs which can be used for either analog or digital
signals. Each port is configured individually via software.
6.4.1
Analog input
The analog inputs are freely configurable as:
Voltage input: 0-24 V DC
Voltage input: 0-1 V DC
Voltage input: 0-100 mV
Current input: 0-20 mA
Resistor (PT1000): 600-1800
Ω
6.4.2
Digital input
The digital inputs are freely configurable as:
Pulse input in accordance with DIN 43864 (S0)
Voltage level input: 0-24 V DC
6.5
Digital input
The digital inputs are freely configurable as:
Pulse input in accordance with DIN 43864 (S0)
Voltage level input: 0-24 V DC
Potential-free contact: 24 V DC / 20 mA