blue’Log X series
87 | 120
14.4.1
cos
φ
(DI) procedure
In this procedure the displacement factor cos
φ
is used as control value.
The specified target value is provided by the grid operator as a digital input signal. This
is possible for example via a remote control system connected to the digital inputs of
the blue’Log. The digital signals are assigned to the specified control values via a
bitmask.
Step 1
In Step 1, the digital inputs used are configured. Digital inputs of the blue’Log are
assigned to the reactive power procedure in the process.
Fig. 68: cos
φ
(DI) Power Control procedure: Selecting the digital inputs
Input box
Meaning
Inputs
Description of the digital input on the blue’Log
+
Adds digital blue’Log interfaces
Retain last value
If enabled, the last valid specified value is retained in the
event of an error. The fallback value loses its validity for
this procedure.