meteocontrol Power Control 03082012 - en
63/78
Fig. 40: Connection ripple control receiver <> WEB`log
(1)
Ripple control receiver
(4)
Digital input DI 3
(2)
Digital input DI1
(5)
Digital input DI 4
(3)
Digital input DI2
(6)
WEB`log
•
If internal WEB`log inputs (WEB`log DIs) are used, feedback signals are
not supported.
•
If Power Control is activated, the digital inputs must not be configured
otherwise by the WEB`log.
•
Ripple control receivers with pulse output are not supported.
A PCU must be used for pulse evaluation.