2.11.2005
Rev. 1.5
Adjustment instructions
48
Select a new parameter using the central dial and wait for 10 seconds, so
the combi-kettle will revert to the standby mode.
6.2
Customer specific parameters, settings and factory presets
The following table contains the parameter values starting from program revision Or54.
The program revision is visible on the temperature display a short moment after switching
the kettle on.
Pr code Function
Display
Value
Facto-
ry pre-
set
Pr10
Default cooking temperature
Temperature
Timing
hPt
0 - 120
80
Pr11
Used temperature unit
Temperature
hEC
hEF
Celsius
Fahrenheit
hEC
Pr12
Default Hold temperature automatically set af-
ter the cooking process
Temperature
Timing
hold
51 - 100
70
Pr13
Central dial selection delay (sec.) after which
the selected value is locked
Temperature
td_2 - td_7
td_5
Pr14
Low-temperature area (51-69°C heating tem-
perature difference
Temperature
hd 0 - hd30
Hd10
Pr15
Mid-temperature area (70-87°C) heating tem-
perature difference
Temperature
nd 0 - nd30
87°C temperature
fixed 100°C
nd30
Pr16
Cooking temperature area ( 88-100°C) heating
temperature difference
Temperature
Hd 0 - Hd13
Hd13
Pr20
Selection and deselection of the short pull back
of the tilting done after releasing the tilting
Temperature
Fbon
FboF
Pull back ON
Pull back OFF
Fbon
Pr21
Selection and deselection of the buzzer signal
used when pausing and ending the mixer
Temperature
Mixer
AL
on
oFF
Buzzer ON
Buzzer OFF
on
Pr30
Water bypass time (min.) of the automatic wa-
ter filling system. Used to empty long water
supply lines of possibly musty water.
Temperature
Water fill
Fti
0 - 10
0 = no bypass flow
done
1
Pr31
Water bypass interval (hours) of the automatic
water filling system. When the interval has
elapsed a new bypass flow is done.
Temperature
Water fill
Fdi
0 - 24
0 = bypass flow al-
ways done
12
Pr40
Default cooling final
Temperature
Info
CFt
0 - 100
30
Pr41
C5 cooling temperature setpoint when tap wa-
ter cooling is changed to Ice Bank
Temperature
Info
C2C3
0-100
0=C2
100=C3
75
Pr42
C5 cooling tap water emptying delay before
Ice Bank emptying delay
Temperature
Info
C5td
0-15
0 = not in use
0
Pr43
Preset time (min.), after which the cooling is
aborted if the temperature doesn’t decrease
any more
Temperature
Info
Cdt2
0 - 4.00
0 = cooling abor-
tion switched off
0.15
Pr50
No longer used
Pr51
Appliance identification code for the
HACCP data collection
Temperature
Mixer
HAC2
0 - 99
0 = HACCP
switched off
0
Pr52
Setting of HACCP data collection interval
(min.)
Temperature
Mixer
HAC3
1, 5 or 10
1
Summary of Contents for PROVENO S 100
Page 2: ......
Page 4: ...2 11 2005 Rev 1 5...
Page 7: ...2 11 2005 Rev...
Page 8: ...2 11 2005 Rev...
Page 62: ...Connection diagram S00123 B3...
Page 63: ...Installation drawing L00115 B3...
Page 64: ...Text part ChillPlus L00114 A4...
Page 65: ...Steam supply recommendations 000030 A4...
Page 68: ......