Multi LAN 350
Operation
22
5.1.2 Channel connection
The Channel connection is used when performance of the complete cabling (including
equipment patch cables) is tested.
On the figure below the maximum network connection can be seen. It consists of:
- Equipment patch cable to the horizontal cross connection point
- horizontal cross connection
- a horizontal cable segment (up to 90m long)
- up to 10m of equipment patch cables with transition connector and outlet connector
In the Channel test the network equipment patch cables influence the result therefore
the test limits are looser than for the Permanent link configuration.
Main unit
Remote
(2)
(1)
(3)
(4)
(5)
(6)
(1) Equipment patch cord
(2) Telecommunication outlet
(3) Consolidation point
(4) Horizontal cable
(5) Horizontal cross connect
(6) Network equipment patch cable
WORK AREA
FLOOR DISTRIBUTION
H
O
R
IZ
O
N
T
A
L
C
A
B
L
IN
G
.......
.......
.......
.......
Maximal test connection for a Channel test