Power Network Application Trainer
– Earthing / Grounding network impedance measurement
119
automatically eliminates neighbourhood connected pylons or parallel connected
earthing systems.
Setup:
– earthing type changed to inductive one
Expected result:
Inductive part of resistance has significant influence, compared only to the resistive
earth type.
Result comparison:
Table 39-2: Result comparison: test object setup vs measurement method
Since transmission pylons are connected via ground wire connection, the HF 25kHz
method is most appropriate one, since it automatically exclude the impedance od
adjacent towers due to high measurement frequency. Ground wire inductance cause,
that impedance of adjacent towers became negligible and only small test current flows
through ground wire connection. Comparing HF measuring method with others we can
conclude, that results measured with 4-pole and S-flex method are smaller, due to the
influence of parallel connected adjacent towers.