Power Network Application Trainer
– Insulation Analysis
204
Note that capacitor of 45 nF charged to 1 kV or capacitor of 8 nF charged
to 5 kV are hazardous live!
Figure 115-3:
Maximum safe capacitance of tested insulation versus test voltage
Select threshold current limit as low as possible.
Don’t touch any part of the test system during the measurement and do not disconnect
test leads until the measurement is finished and the DUT discharged.
Figure 116-3:
Discharging of insulating material (Ciso = 100 nF, Utest = 5 kV)
METREL test equipment makes automatic discharge of the test circuit at the end of
the test.