208
8.1 Insulation resistance measurement on the cable simulation
test object
Note: Maximum applied test voltage to the test object is 5kV!
Do not apply higher test voltage!
Hint
The lower limit of insulation resistance may often be established according to
the one mega-
ohm rule
:
Insulation resistance should be at least one mega-ohm for each kilovolt of operating
voltage, but not less than one mega-ohm.
For example, a motor rated at 5 kV working voltage should have a minimum resistance
of 5 MΩ.
Exercise 1: Insulation resistance test (Spot test)
This is the simplest and fastest way of insulation resistance testing. Unfortunately, only one
test, with no prior tests, can be only a rough guide as to how good or bad the insulation is. In
this test the instrument is connected across the insulation of the tested item. A test voltage is
applied for a fixed period of time, usually a reading is taken after 1 minute.
Figure 118-3: Measurement setup for insulation testing