Power Network Application Trainer
– Insulation Analysis
215
Exercise 3: Step Voltage Test
Figure 120-3: Step voltage test measuring setup
In Step Voltage test, the insulation is measured in five equal time periods with test
voltages from one fifth of the final test voltage up to full scale. This function illustrates
the relationship of a materials Insulation resistance and its applied voltage.
Method used
Simulated condition
Expected result
Un=5kV; Timer=05:00
R1=1.94GΩ; U1=1.03kV
R2=2.59 GΩ; U1=2.02 kV
R3=3.09 GΩ; U1=3.02 kV
R4=3.66 GΩ; U1=4.01kV
R5=4.08 GΩ; U1=5,01 kV
Table 74-3: Step voltage test setup/result presentation
Measuring procedure
1. Connection set up is the same as it is performed under Exercise 1.
2. Under
MAIM MENU
MEASUREMENTS
menu select
Step Voltage Test
measurement function
Summary of Contents for MI 3298
Page 55: ...Power Network Application Trainer Earthing Grounding network impedance measurement 55 ...
Page 56: ...Power Network Application Trainer Earthing Grounding network impedance measurement 56 ...
Page 124: ...Power Network Application Trainer Earthing Grounding network impedance measurement 124 ...
Page 228: ...MI 3290 Earth Analyser 228 ...
Page 229: ...MI 3280 Digital Transformer Analyser 229 ...
Page 230: ...MI 3280 Digital Transformer Analyser 230 ...
Page 231: ...MI 3250 MicroOhm 10A 231 ...
Page 232: ...MI 3205 TeraOhmXA 5kV 232 ...