119
Measured R
E
with enabled error S23 (upper left), S24 (upper right) and combination of
both
– S23 + S24 (bottom).
2.8.2.2 Exercise No. 2.8-2: Earth Resistance Measurement
– two clamp
method
This method is intended for measuring earth resistance in a TN earthing systems or when
lightning systems and earth loops have to be checked.
Measuring procedure
1
To measure the earth resistance in a TN system or lightning systems and earth loops
select the
2-clamp
function in the
Earth
section.
2
Set the maximum allowed earth resistance by clicking in the bottom left dark grey
corner.