Power and Voltage Quality Trainer
AD 2
– MI 3399
169
Figure 4-41: Captured voltage interrupt (RMS values)
For further analysis, the user can observe also the waveform shape of the interrupt.
From this graph, interrupt phase shift or interrupt starting point on the wave can be
seen. Figure below represents such a view.
Figure 4-42: Captured waveform of voltage interrupt
Summary of Contents for MI 3399
Page 27: ...Electrical Installation Safety Trainer AD 1 MI 3399 27...
Page 46: ...Electrical Installation Safety Trainer AD 1 MI 3399 46 3 Exit settings...
Page 74: ...Electrical Installation Safety Trainer AD 1 MI 3399 74...
Page 197: ...Power and Voltage Quality Trainer AD 2 MI 3399 197 Figure 4 89 Transient Chart view...
Page 204: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 204...
Page 249: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 249...
Page 250: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 250 AD 4 MI 3399 PV Photovoltaic Systems Trainer...