Power and Voltage Quality Trainer
AD 2
– MI 3399
187
Figure 4-75: Flicker in time chart
4.9 Exercise 9
– Inrush recording
In this exercise, we will show how the instrument should be setup in order to capture
current inrush events. Inrush current typically occurs during a motor start event. Before
start, please set the switch S8 in the Application Trainer to ON as shown in the table
below. The remaining switches should be set to OFF.
Switch
Description
State
S8
Inrush
ON
The Application Trainer will emulate an inrush event with the following parameters:
Fundamental voltage: U1=U2=U3=230V
Fundamental current: I1=I2=I3=1000A
Inrush current on I1 with max. current 1700A and 200msec duration, repeated
every 10 second
Load type: Inductive
Load character: Motor Load (Consumption of electrical power)
Frequency: 50/60 Hz
4.9.1 Real time measurements
Usually inrush events can be triggered manually (by starting a motor). However inrush
events are sometimes out of our control and occur randomly. It is recommended to
start with observing maximum (MAX), minimum (MIN) and RMS current in the
MEASRUREMENTS
U,I,f menu, as shown below. Before observing the RESET key
(F2) should be pressed. In this exercise, maximum current generated by the
Summary of Contents for MI 3399
Page 27: ...Electrical Installation Safety Trainer AD 1 MI 3399 27...
Page 46: ...Electrical Installation Safety Trainer AD 1 MI 3399 46 3 Exit settings...
Page 74: ...Electrical Installation Safety Trainer AD 1 MI 3399 74...
Page 197: ...Power and Voltage Quality Trainer AD 2 MI 3399 197 Figure 4 89 Transient Chart view...
Page 204: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 204...
Page 249: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 249...
Page 250: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 250 AD 4 MI 3399 PV Photovoltaic Systems Trainer...