Power and Voltage Quality Trainer
AD 2
– MI 3399
189
As soon as current on any cannel reaches the given LEVEL, it will start recording.
Active recording will be indicated in the status bar, with a red icon
.
Figure 4-78: Observing current waveform during inrush capturing
After an inrush event is captured it can be observed in the RECORDERS
MEMORY
LIST menu, as shown in the figures below.
Figure 4-79: Real time measurements of current inrush
4.9.3 Downloading and observing recorded data in PowerView
The recorded data can be imported into PowerView for further analysis. Please note
that prior this step PowerView should be installed and set up as described in section
1.2 PowerView installation and setup.
Open Pow
erView and click on the “Download” button on the toolbar. A new window
will appear with the instrument's information and list of available records (see figure
below). Select the desired records (current selections are coloured green), then click
on the “Start importing” button.