198
4.11 Exercise 11
– Phase (switch) failure
This practical example will reproduce an event where two phases are interchanged
during switching power feeding form one transformer to another. During such an event
excessive current inrush can occur, which could cause feeder tripping.
L1
L2
L3
L1
L2
L3
L1 L2 L3
Transformer 2
Fe
ed
in
g
Phase L2 and L3 are
interchanged during switch
occurance
Figure 4-90: Phase switch
In order to simulate such an event, please set the switch S10 in the Application Trainer
to ON as shown in the table below. The remaining switches should be set to OFF. The
Application Trainer will switch between phases L2 and L3 every 10 seconds.
Switch
Description
State
S10
Phase (switch) failure
ON
In practice we usually don’t know where the problem is; therefore we recommend to
start observing voltage, current and THD. This can be done by entering the U,I,f MENU
in the MEASUREMENT MENU, as shown below.
Figure 4-91: Real time measurements of voltage and current
Summary of Contents for MI 3399
Page 27: ...Electrical Installation Safety Trainer AD 1 MI 3399 27...
Page 46: ...Electrical Installation Safety Trainer AD 1 MI 3399 46 3 Exit settings...
Page 74: ...Electrical Installation Safety Trainer AD 1 MI 3399 74...
Page 197: ...Power and Voltage Quality Trainer AD 2 MI 3399 197 Figure 4 89 Transient Chart view...
Page 204: ...PAT Appliances Machines Safety Trainer AD 3 MI 3399 204...
Page 249: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 249...
Page 250: ...PV Photovoltaic Systems Trainer AD 4 MI 3399 250 AD 4 MI 3399 PV Photovoltaic Systems Trainer...