Figure 4-36: Testing of RCD in electrical installation
4.5.3.4 Discharge Time
If large capacitors in machines are disconnected from supply there is often a remaining
(residual) charge on internal machine components. Live parts having a residual voltage
greater than 60 V after the supply has been disconnected, shall be discharged to 60 V or
less within a time period of 5 s after disconnection of the supply.
For plugs or similar devices with exposed conductors (for example pins) if plugged out it
shall be discharged to 60 V or less within a time period of 1 s after disconnection of the
supply.
Figure 4-37: Discharge time test
4.5.3.5 Functional test
Functional check explores if the machine is working properly. Following items should be
checked while the machine is operating:
Temperature regulators, monitors.
RCDs and other disconnection devices.
Operation of functional disconnecting devices.
Operation of switches, lamps, keys.
Rotating parts, motors, pumps.