PAT Appliances & Machines Safety Trainer
AD 3
– MI 3399
241
5.3 Portable appliance of class 2
– Receiver
Simulates
Error value
Error off
Error on
Simulation between contacts Measurement taken
Error off
Error on
Error 1
Insulation fault
Error value
>20 MΩ
238 kΩ
L pin on socket (2) and
accessible isolated metal
part (1)
Insulation
500V
DC
(probe)
>20 MΩ
0,238 MΩ
Touch Leakage 230 V
AC
0,00 mA
0,97 mA
Subleakage (probe)
0,00 mA
0,97 mA
Error 2
Functional fault
Functional
/
interruptions
Functional
Functional
/
interruptions
Table 5-2: Description of simulated faults / relevant tests