PAT Appliances & Machines Safety Trainer
AD 3
– MI 3399
247
5.9 Low voltage switchgear
Simulates
Error value
Error off Error on
Simulation between contacts
Measurement taken Error off Error on
Error 1
Loose contact of PE conductor
Error value
0,02 Ω
0,41 Ω
PE input connection (1) and earthed metal
part (2)
Earth Bond
0,02 Ω
0,41 Ω
Error 2
Insulation fault
Error value
>20 MΩ 1.88 MΩ
L, (2) and PE connection (3)
Insulation 1000 V
DC
>20 MΩ
1.880
M
Ω
Withstanding 2500 V
AC
0,1 mA
1,4 mA
Error 3
Excessive charge on filter capacitors
Error value
4.7nF
100
MΩ
100 nF
100
MΩ
L and N on input connections (2)
Discharging time*
cca 0,4 s cca 9 s
Table 5-8: Description of simulated faults / relevant tests
* Measured with CE Multitester (resistance of measuring circuit 40MΩ). Discharging times
for other test instruments can vary, depending on their internal resistance.