Electrical Installation Safety Trainer
AD 1 - MI 3399
48
Figure 2-3: Measuring Z
Line
in Application Trainer’s switchboard with cables
Figure 2-4: Measuring Z
Line
in the Application Trainer with the schuko commander on
an IT system
2.2.1 Background of measurements
Line impedance includes the resistive and inductive part in the short circuit loop. The
main part of inductivity comes from the power transformers’ inductances.
The resistance part mainly comes from copper wiring in the loop (transformer, phase
and neutral conductors).
In general the inductive part can be neglected if the loop impedance > 0.4 Ω.
In applications where the measurement is carried out in close proximity to the power
transformer (< 50m) the inductivity can be of a similar value than the resistance part.