Electrical Installation Safety Trainer
AD 1 - MI 3399
56
E.g. if we use a B6 fuse inside a residential building with a 3-phase system the
following fuse settings should be set:
3
Whenever a fuse parameter setting is changed, the prospective fault current (I
PSC
)
limit is set automatically.
4
If the commander is to be used, plug the commander into the appropriate schuko
outlet. If the commander is not used connect the L
x
and L
y
cables to the appropriate
conductors.
5
Press the
START
key.
Expected results
The prospective short circuit current (I
PSC
) is calculated as:
𝑰
𝑷𝑺𝑪
=
𝑼
𝑵
𝒁
𝑴𝑬𝑨𝑺𝑼𝑹𝑬𝑫