Electrical Installation Safety Trainer
AD 1 - MI 3399
78
2.4.2 Exercises
2.4.2.1 Exercise No. 2.4-1: RCD trip-out time, current and contact
voltage measurements
Measuring connection topology
Figure 2-27: RCD measurement in a 1-phase TT system
Measuring procedure
1
To measure the contact voltage
U
C
of a TT system select the
RCD U
C
test.
2
To measure the trip-out time
t
ΔN
of a TT system select the
RCD t
test.
3
To measure the trip-out current
I
Δ
of a TT system select the
RCD I
test.
4
To perform all RCD measurements (
U
C
,
t
ΔN
,
I
Δ
) in one easy step select the
RCD
Auto
test.