Electrical Installation Safety Trainer
AD 1 - MI 3399
88
2
Set the minimum allowed resistance or the maximum allowed short circuit current
on both lines by clicking in the bottom left dark grey corner.
3
If a schuko commander is to be used, plug the commander into the appropriate
outlet. If the cables are used, connect all cables appropriately
– the PE cable to
the PE conductor, the N cable to Line2 and the L cable to Line1.
4
Press the
START
key.
Expected results
In a normal situation the IMD issue an alert when the maximum leakage current rises
above 4,4 mA (if current is being tested) or the fault resistance falls under 35 k
Ω (when
earth resistance is being tested). If the alarm sounds within the specified values then
the test should be marked as passed, otherwise as failed.