Electrical Installation Safety Trainer
AD 1 - MI 3399
93
2
Set the minimum allowed insulation resistance by clicking in the bottom left dark
grey corner.
3
If a schuko commander is to be used, plug the commander into the appropriate
outlet. If the cables are used, connect all cables appropriately
– the PE cable to
the PE conductor, the N cable to Line2 and the L cable to Line1.
During the measurement, check the insulation resistance between all conductors
(L
X
-L
Y
, L-N, L-PE. N-PE).
4
Press the
START
key.
Expected results
In a normal situation, the insulation resistance in a circuit should be well above 1 M
Ω
and above 0.5 M
Ω in a PELV/SELV environment.