Electrical Installation Safety Trainer
AD 1 - MI 3399
95
2
Set the minimum allowed insulation resistance by clicking in the bottom left dark
grey corner.
3
If a schuko commander is to be used, plug the commander into the appropriate
outlet. If the cables are used, connect all cables appropriately
– the PE cable to
the PE conductor, the N cable to Line2 and the L cable to Line1.
During the measurement, check the insulation resistance between all conductors
(L
X
-L
Y
, L-N, L-PE. N-PE).
4
Press the
START
key.
Expected results
Conduct this measurement at the switchboard. After disabling the RCD measure all
possible insulations resistances between all conductors as described above. To verify
all circuits connected to this RCD simply perform all tests on the output side of the
RCD. If all tests pass then insulation is sufficient between all conductors. In such case
the output of the measuring device should show the same result as the picture below.