background image

Doc# 

M9005 • REV N

 (May 2017) Page 

10 of 12

 

b) Verify current output with separate current meter connected in series with the 4-20 mA 

output and the receiving instrument input. Verify the current is correct. Current output with 

zero vibration should be 4.0 mA. A 20 mA current represents full scale vibration.

3. The unit does not respond to a vibration input during the first few seconds of operation.

a) The startup time delay circuit prevents the transmitter from reacting to a vibration input 

during the startup delay time period. The standard time delay is fixed at 30 seconds. If the 

unit has the optional variable startup delay, it can be varied from 1 to 30 seconds. The cur

-

rent output is held at 4.0 mA and the display is held at 000 until the startup time delay has 

expired.

4. The unit trips the limits shortly after applying power to the unit.

a) Units with an adjustable startup time delay which is set close to the minimum setting can 

have the limits trip at power up. This is due to the settling time of the circuitry in the Model 

SW6000 switch. If a short startup delay is desired, it is suggested that power first be applied 

to the unit for a minimum of 20 seconds. Power may also be applied continuously. The limits 

may need to be reset depending on the particular application. Afterwards, the machine can 

be started in a normal fashion.

5. The unit is functioning but accuracy is in question.

a) The vibration output can be verified by placing a separate vibration pickup near the base 

of the Model SW6000 and comparing the two readings. Remember that the vibration meter 

or analyzer must utilize true RMS detection and have similar frequency response character

-

istics. Even then, significant differences can exist due to dissimilar sensor orientations, hand

-

held versus rigid mounting, meter or analyzer time constant differences, and other factors. 

The calibration of the Model SW6000 should be verified on a yearly basis as a minimum.

b) Alternately, the unit can be removed and placed on a calibrated shaker system in order to 

verify the calibration. Metrix Instrument Co. can provide factory calibration traceable to NIST 

standards.

6. The unit does not appear to be functioning.

a) Ensure that all wiring connections to the terminal block are correct, terminal screws are 

tight and that the correct voltage is present at the terminal block power (Vin) terminals. DC 

voltage polarity is arbitrary. Refer to Figure 4 and Product Identification page 2 for specific 

details. If power is applied, the LCD display (if present) should be functioning, and the cur

-

rent output should be between 4.0 and 20.0 mA.

Summary of Contents for SW6000

Page 1: ...s standard configuration the SW6000 is an economical single set point vibration switch with standard features and packaged in industrial grade housing with available haz ardous area certifications Ful...

Page 2: ...d Mount Unit requires a tapped hole see Metrix Datasheet doc 1009462 Option F or use a Metrix model 7084 flange mount adapter If an NPT mounting stud is selected the stud will tighten before the switc...

Page 3: ...ocations NOTES 1 Diagrams show all available options see SW6000 datasheet doc 1009462 to verify options on your particular unit 2 On Single Limit Models use Load Limit Two 2 Baseefa Special Conditions...

Page 4: ...the shield should be tied to common only at the receiver end A cable consist ing of separate shielded twisted pairs can also be used For the dynamic signal output the capacitance of the cable run mus...

Page 5: ...See Figure 2 b M2 M3 and remote reset contacts must each be isolated Figure 4 Parallel connection of two SW6000 a Set each SW6000 for N C normally closed operation See Figure 2 b M2 M3 and remote rese...

Page 6: ...ts if ap plicable 4 20 mA Current Source Output optional If the optional 4 20 mA output is installed it may be connected to a remote receiver as shown on the wiring diagram see Figure 2 This output is...

Page 7: ...re that the analyzer is configured with the same frequency response as the SW6000 and with the same unit of measure i e ips pk To prevent tampering there are no user accessible adjustments available f...

Page 8: ...t will trip The adjustment has a range of 10 to 110 of the full scale vibration level A midscale adjustment corresponds to a 50 vibration level limit The limit setting can be set precisely by measurin...

Page 9: ...it LED should turn on after the set trip delay expires REMEMBER to return the limit setting to the original position after this test c If the LED is lit but the limit is not functioning check to make...

Page 10: ...continuously The limits may need to be reset depending on the particular application Afterwards the machine can be started in a normal fashion 5 The unit is functioning but accuracy is in question a T...

Page 11: ...AS DEBRANCHER TANT QUE LE CIRCUIT EST SOUS TENSION A MOINS QU IL NE S AGISSE D UN EMPLACEMENT NON DAN GEREUX ATEX Approval Europe ATEX Markings II 2G Ex d IIB H2 T4 Gb Ta 20 C to 85 C no display Ta 10...

Page 12: ...dards to ensure safe and reliable operation when used as intended Due to its nature this equipment may contain small quantities of substances known to be hazardous to the environment or to human healt...

Reviews: