WIRING

Terminal Wiring

If you have selected the optional display, the display circuit board must be removed (two 

screws) to expose the terminal strips.  The display board cable should not be disconnected.  

Simply place the display board out of the way to allow wiring to the terminal strips.  The 

display may be reinstalled in any of the four possible orientations. Connection to the unit is 

through one or two conduit entries (See Metrix Drawing 9030). The cable gland or conduit 

entries shall be in accordance with 13.1 of EN60079-1 and IEC60079-1. The user must provide 

appropriate seal and sealing materials for the rates installation. Unused conduit entries must 

be plugged with a plug that conforms to Clause 13.2 of EN60079-1 and IEC60079-1. The inter

-

nal ground connector allows for the connection of a 14 AWG wire. This has a cross section of 2 

mm

2

. The external ground terminal can accommodate a 10 AWG wire that has an cross section 

area of 5 mm

2

. It is comprised of an M5 bolt with two flat washers and one lock washer.

Refer to Figure 2 for wiring information.  For incoming power and switch output(s) use ap

-

proved wire of 14 AWG (1.5 mm

2

) or smaller.  

For the current and dynamic signal outputs, a shielded twisted pair is recommended.  By 

convention, the shield should be tied to common only at the receiver end.  A cable consist

-

ing of separate shielded twisted pairs can also be used.  For the dynamic signal output, the 

capacitance of the cable run must not exceed 0.03 

m

F (typically 1000 ft).

NOTE: 

On ATEX/IECEx approved units, a locking set 

screw must be loosened prior to lid removal.

CAUTION: 

Conduit seals are highly recommended to prevent the entry 

of moisture into the switch. Moisture will damage the switch and void 

the warranty. Internal and external protective earth connections must 

be connected to the installation protective earth circuits.

Power Wiring

It is highly recommended that all power and triac/FET wiring be routed separately from the 

external sensor, the dynamic signal and 4-20mA wiring in order to reduce AC/transient noise 

pickup.  The power required is indicated on the nameplate.  The voltage supply must be 

within the following limits:

24 VDC:  

20 VDC to 28 VDC   

115 VAC: 

 95 VDC to 125 VAC, 50/60 Hz 

230VAC: 

 190 VDC to 250 VAC, 50/60 Hz

Polarity does not need to be observed when wiring for DC power.  The preferred method of 

operation is to continuously apply power to the SW6000. If power is to be applied as a part 

of the machine startup sequence it is advisable to apply power to the SW6000 30 seconds 

prior to starting the machine in order to allow the electronics circuits to stabilize. This is 

particularly important if the adjustable startup delay option is utilized and the delay is set to 

less than 20 seconds.

Summary of Contents for SW6000

Page 1: ...s standard configuration the SW6000 is an economical single set point vibration switch with standard features and packaged in industrial grade housing with available haz ardous area certifications Ful...

Page 2: ...d Mount Unit requires a tapped hole see Metrix Datasheet doc 1009462 Option F or use a Metrix model 7084 flange mount adapter If an NPT mounting stud is selected the stud will tighten before the switc...

Page 3: ...ocations NOTES 1 Diagrams show all available options see SW6000 datasheet doc 1009462 to verify options on your particular unit 2 On Single Limit Models use Load Limit Two 2 Baseefa Special Conditions...

Page 4: ...the shield should be tied to common only at the receiver end A cable consist ing of separate shielded twisted pairs can also be used For the dynamic signal output the capacitance of the cable run mus...

Page 5: ...See Figure 2 b M2 M3 and remote reset contacts must each be isolated Figure 4 Parallel connection of two SW6000 a Set each SW6000 for N C normally closed operation See Figure 2 b M2 M3 and remote rese...

Page 6: ...ts if ap plicable 4 20 mA Current Source Output optional If the optional 4 20 mA output is installed it may be connected to a remote receiver as shown on the wiring diagram see Figure 2 This output is...

Page 7: ...re that the analyzer is configured with the same frequency response as the SW6000 and with the same unit of measure i e ips pk To prevent tampering there are no user accessible adjustments available f...

Page 8: ...t will trip The adjustment has a range of 10 to 110 of the full scale vibration level A midscale adjustment corresponds to a 50 vibration level limit The limit setting can be set precisely by measurin...

Page 9: ...it LED should turn on after the set trip delay expires REMEMBER to return the limit setting to the original position after this test c If the LED is lit but the limit is not functioning check to make...

Page 10: ...continuously The limits may need to be reset depending on the particular application Afterwards the machine can be started in a normal fashion 5 The unit is functioning but accuracy is in question a T...

Page 11: ...AS DEBRANCHER TANT QUE LE CIRCUIT EST SOUS TENSION A MOINS QU IL NE S AGISSE D UN EMPLACEMENT NON DAN GEREUX ATEX Approval Europe ATEX Markings II 2G Ex d IIB H2 T4 Gb Ta 20 C to 85 C no display Ta 10...

Page 12: ...dards to ensure safe and reliable operation when used as intended Due to its nature this equipment may contain small quantities of substances known to be hazardous to the environment or to human healt...

Reviews: