background image

Doc# 

M9005 • REV N

 (May 2017) Page 

5 of 12

 

Alarm Limit Triac Output Wiring

The triac output(s) are electro-optically isolated from each other, power, and the internal 

circuit.  These are medium-power devices with high immunity to electrical transients. If 

desired, each triac can be supplied from an AC voltage source different from the main sup

-

ply. The triacs can be connected in series with the triacs of other units. See Figure 4. Parallel 

connection of two switches doubles the triac holding (minimum load) current requirements. 

The maximum triac supply voltage is 250 VAC.  The worst case triac leakage (off) current is 2 

mA.  The maximum triac holding current is 35 mA at 25°C (60mA at -40°C) which requires that 

the relay pull-in current have a greater value. Do not use a DC supply. The triacs can be set for 

N.C. or N.O. operation by positioning the Limit 1 / Limit 2 switches accordingly.

Typical Control Circuits SW6000 w/AC Power Wired to Interrupt Motor Starter 

 

(series connection)

a. Set each SW6000 for N.C. (normally closed) operation. (See Figure 2)

b. M2, M3 and remote reset contacts must each be isolated.

Figure 4: Parallel connection of two SW6000

a. Set each SW6000 for N.C. (normally closed) operation. (See Figure 2)

b. M2, M3 and remote reset contacts must each be isolated.

Alarm Limit FET Output Wiring (optional)

The optional FET limit output(s) provide a low leakage switch for DC inputs to PLC’s or other 

devices. Do not use on an AC supply. Observe proper polarity when wiring the FET(s) (See 

figure 2). Damage to the FET(s) will result from improper wiring. As with the triacs, the FET(s) 

can be set for N.C. or N.O. operation by positioning the Limit 1/Limit 2 switches accordingly.

Limit Trip Delay

The base unit has an adjustable (1-15 sec.) limit trip delay. The vibration level must be con

-

tinuously above the limit setting for the duration of the time delay before the output devices 

switch. The 4-20 mA output is not affected by this time delay. To reset the limit output 

devices, the internal reset push-button or the optional external reset push-button must be 

pressed. Remote reset by a N.O. push-button or momentary contacts may be made by wiring 

to the remote reset terminals. Note that the vibration level must be below the trip level for 

the reset to function.

Summary of Contents for SW6000

Page 1: ...s standard configuration the SW6000 is an economical single set point vibration switch with standard features and packaged in industrial grade housing with available haz ardous area certifications Ful...

Page 2: ...d Mount Unit requires a tapped hole see Metrix Datasheet doc 1009462 Option F or use a Metrix model 7084 flange mount adapter If an NPT mounting stud is selected the stud will tighten before the switc...

Page 3: ...ocations NOTES 1 Diagrams show all available options see SW6000 datasheet doc 1009462 to verify options on your particular unit 2 On Single Limit Models use Load Limit Two 2 Baseefa Special Conditions...

Page 4: ...the shield should be tied to common only at the receiver end A cable consist ing of separate shielded twisted pairs can also be used For the dynamic signal output the capacitance of the cable run mus...

Page 5: ...See Figure 2 b M2 M3 and remote reset contacts must each be isolated Figure 4 Parallel connection of two SW6000 a Set each SW6000 for N C normally closed operation See Figure 2 b M2 M3 and remote rese...

Page 6: ...ts if ap plicable 4 20 mA Current Source Output optional If the optional 4 20 mA output is installed it may be connected to a remote receiver as shown on the wiring diagram see Figure 2 This output is...

Page 7: ...re that the analyzer is configured with the same frequency response as the SW6000 and with the same unit of measure i e ips pk To prevent tampering there are no user accessible adjustments available f...

Page 8: ...t will trip The adjustment has a range of 10 to 110 of the full scale vibration level A midscale adjustment corresponds to a 50 vibration level limit The limit setting can be set precisely by measurin...

Page 9: ...it LED should turn on after the set trip delay expires REMEMBER to return the limit setting to the original position after this test c If the LED is lit but the limit is not functioning check to make...

Page 10: ...continuously The limits may need to be reset depending on the particular application Afterwards the machine can be started in a normal fashion 5 The unit is functioning but accuracy is in question a T...

Page 11: ...AS DEBRANCHER TANT QUE LE CIRCUIT EST SOUS TENSION A MOINS QU IL NE S AGISSE D UN EMPLACEMENT NON DAN GEREUX ATEX Approval Europe ATEX Markings II 2G Ex d IIB H2 T4 Gb Ta 20 C to 85 C no display Ta 10...

Page 12: ...dards to ensure safe and reliable operation when used as intended Due to its nature this equipment may contain small quantities of substances known to be hazardous to the environment or to human healt...

Reviews: