background image

Doc# 

M9005 • REV N

 (May 2017) Page 

6 of 12

 

Startup Trip Delay

Some machines generate vibration levels during startup which are higher than normal 

running levels. These high vibration levels can exceed the Alarm Trip Limits which are set 

above the normal running vibration level. The standard SW6000 has a fixed time delay which 

inhibits alarm trips for 30 seconds from the closing of the startup contacts. 

An optional adjustable startup trip delay (1-30 sec.) permits the Alarm Trip Limits to become 

operative in less than 30 seconds. Protection of machines with short startup times can be 

improved by utilizing the adjustable Startup Trip delay.

The Startup Trip Delay is triggered by closing a set of contacts (momentary or continuous) 

connected to the startup terminals. The contacts must be opened before the internal startup 

delay timer can be initiated again. Connecting these terminals to a set of isolated auxiliary 

N.O. contacts in a motor starter is a method commonly used to initiate the startup trip delay. 

The 4-20 mA current output is inhibited (set to 4.0 mA) during the startup trip delay.

Remote Reset Wiring (optional)

If remote reset capability is desired, connect Reset terminals (see Figure 2) to a remotely 

located, momentary N.O. pushbutton switch. Observe hazardous area requirements if ap

-

plicable.

4-20 mA Current Source Output (optional)

If the optional 4-20 mA output is installed, it may be connected to a remote receiver, as 

shown on the wiring diagram (see Figure 2). This output is a current source (at 15VDC) and 

requires no external loop power supply. Full scale current (20 mA) corresponds to the full 

scale vibration response marked on the face plate. A current of 4.0 mA represents a zero 

vibration condition. The maximum load resistance is 600 ohms. In high electrical noise loca

-

tions a shielded, twisted pair cable is recommended.

FORMULA: 

 

 

 

 X Full scale vibration = Actual vibration

EXAMPLE: 

Measured mA

Full Scale Vibration Actual Vibration

4.0

1.0 ips, peak

0.0 ips, peak

12.0

1.0 ips, peak

0.5 ips, peak

20.0

1.0 ips, peak

1.0 ips, peak

Dynamic Outputs

The sensor (acceleration) signal is available at the terminal block and is capable of driving 

a cable with a capacitance of up to 0.03 

m

F (typically 300m/1000 feet). Longer runs with 

greater than 0.03 

m

F of capacitance can be used without the buffer becoming unstable. 

However, the frequency response will be reduced due to the increased capacitance.

RECEIVER CONFIGURATION / CALIBRATION

Signal Conditioning Module Output: 4 - 20 mA Source Option

The SW6000 can be factory configured to provide a 4 - 20 mA current source output propor

-

tional to the specified full scale vibration response (velocity or displacement). Figure 5 shows 

suggested programming for a 4-20 mA receiver (PLC, DCS, monitor or computer).

Measured mA - 4mA

20mA - 4mA

Summary of Contents for SW6000

Page 1: ...s standard configuration the SW6000 is an economical single set point vibration switch with standard features and packaged in industrial grade housing with available haz ardous area certifications Ful...

Page 2: ...d Mount Unit requires a tapped hole see Metrix Datasheet doc 1009462 Option F or use a Metrix model 7084 flange mount adapter If an NPT mounting stud is selected the stud will tighten before the switc...

Page 3: ...ocations NOTES 1 Diagrams show all available options see SW6000 datasheet doc 1009462 to verify options on your particular unit 2 On Single Limit Models use Load Limit Two 2 Baseefa Special Conditions...

Page 4: ...the shield should be tied to common only at the receiver end A cable consist ing of separate shielded twisted pairs can also be used For the dynamic signal output the capacitance of the cable run mus...

Page 5: ...See Figure 2 b M2 M3 and remote reset contacts must each be isolated Figure 4 Parallel connection of two SW6000 a Set each SW6000 for N C normally closed operation See Figure 2 b M2 M3 and remote rese...

Page 6: ...ts if ap plicable 4 20 mA Current Source Output optional If the optional 4 20 mA output is installed it may be connected to a remote receiver as shown on the wiring diagram see Figure 2 This output is...

Page 7: ...re that the analyzer is configured with the same frequency response as the SW6000 and with the same unit of measure i e ips pk To prevent tampering there are no user accessible adjustments available f...

Page 8: ...t will trip The adjustment has a range of 10 to 110 of the full scale vibration level A midscale adjustment corresponds to a 50 vibration level limit The limit setting can be set precisely by measurin...

Page 9: ...it LED should turn on after the set trip delay expires REMEMBER to return the limit setting to the original position after this test c If the LED is lit but the limit is not functioning check to make...

Page 10: ...continuously The limits may need to be reset depending on the particular application Afterwards the machine can be started in a normal fashion 5 The unit is functioning but accuracy is in question a T...

Page 11: ...AS DEBRANCHER TANT QUE LE CIRCUIT EST SOUS TENSION A MOINS QU IL NE S AGISSE D UN EMPLACEMENT NON DAN GEREUX ATEX Approval Europe ATEX Markings II 2G Ex d IIB H2 T4 Gb Ta 20 C to 85 C no display Ta 10...

Page 12: ...dards to ensure safe and reliable operation when used as intended Due to its nature this equipment may contain small quantities of substances known to be hazardous to the environment or to human healt...

Reviews: