background image

Doc# 

M9005 • REV N

 (May 2017) Page 

8 of 12

 

Determining Output Voltage

If it is desired to determine either the acceleration or velocity amplitude when one measure

-

ment is unknown, the following formulas can be employed.

If g’s (A) are known and you wish to determine the velocity output:

If velocity is known and you wish to determine the displacement output:

If g’s (A) are known and you wish to determine the displacement output:

V = ips, peak

F = RPM

A = g peak

D = mils, peak-to-peak

USER ADJUSTMENTS

Limit Trip Delay

The Limit Trip Delay adjustment allows the user to set the time delay from 1 to 15 seconds. 

This is useful in avoiding false trips from transient conditions while the machine is running.

Adjustable Startup Trip Delay (optional)

The optional Startup Trip Delay adjustment allows the user to set the time delay from 1 to 

30 seconds. This is useful in tailoring the Startup Trip Delay for a particular machine’s startup 

vibration characteristics.

Limit Settings

The Limit Setting adjustment allows the user to set the vibration levels at which a limit will 

trip. The adjustment has a range of -10% to 110% of the full scale vibration level. A midscale 

adjustment corresponds to a 50% vibration level limit. The limit setting can be set precisely 

by measuring the limit voltage with a DVM. The test points for measuring this voltage are 

labeled TP3 (Limit 2), TP4 (limit 1) and COM (common) on Figure 2. The DC voltage repre

-

sents a percentage of full scale. For example, .46 VDC would represent a limit setting of 46% 

of full scale. Turning the adjustment to its minimum value (CCW) allows the user to test the 

trip circuitry, including LED’s, time delays and triac (FET) switches.

AUTO RESET

The switch outputs (triacs or FETs) are configured at the factory for latching operation. The 

switch outputs can be configured for non-latching operation so they automatically reset when 

the vibration level falls below the alarm limit threshold. To do this, remove power to the 

unit. Remove the transmitter cover and the display board if present. Refer to Figure 7. (Move 

both jumpers to the auto position). Reassemble the display board and transmitter cover. The 

switch outputs will now reset when the vibration level falls below the alarm limits.

V= 

3687

 x A

         F

D= 19,100 x V

           F

D=  

8383 

 

2

 

x V

           F

( )

Example V=      3687     x 0.5g = 1.02 ips, peak

 

     1800 RPM

Summary of Contents for SW6000

Page 1: ...s standard configuration the SW6000 is an economical single set point vibration switch with standard features and packaged in industrial grade housing with available haz ardous area certifications Ful...

Page 2: ...d Mount Unit requires a tapped hole see Metrix Datasheet doc 1009462 Option F or use a Metrix model 7084 flange mount adapter If an NPT mounting stud is selected the stud will tighten before the switc...

Page 3: ...ocations NOTES 1 Diagrams show all available options see SW6000 datasheet doc 1009462 to verify options on your particular unit 2 On Single Limit Models use Load Limit Two 2 Baseefa Special Conditions...

Page 4: ...the shield should be tied to common only at the receiver end A cable consist ing of separate shielded twisted pairs can also be used For the dynamic signal output the capacitance of the cable run mus...

Page 5: ...See Figure 2 b M2 M3 and remote reset contacts must each be isolated Figure 4 Parallel connection of two SW6000 a Set each SW6000 for N C normally closed operation See Figure 2 b M2 M3 and remote rese...

Page 6: ...ts if ap plicable 4 20 mA Current Source Output optional If the optional 4 20 mA output is installed it may be connected to a remote receiver as shown on the wiring diagram see Figure 2 This output is...

Page 7: ...re that the analyzer is configured with the same frequency response as the SW6000 and with the same unit of measure i e ips pk To prevent tampering there are no user accessible adjustments available f...

Page 8: ...t will trip The adjustment has a range of 10 to 110 of the full scale vibration level A midscale adjustment corresponds to a 50 vibration level limit The limit setting can be set precisely by measurin...

Page 9: ...it LED should turn on after the set trip delay expires REMEMBER to return the limit setting to the original position after this test c If the LED is lit but the limit is not functioning check to make...

Page 10: ...continuously The limits may need to be reset depending on the particular application Afterwards the machine can be started in a normal fashion 5 The unit is functioning but accuracy is in question a T...

Page 11: ...AS DEBRANCHER TANT QUE LE CIRCUIT EST SOUS TENSION A MOINS QU IL NE S AGISSE D UN EMPLACEMENT NON DAN GEREUX ATEX Approval Europe ATEX Markings II 2G Ex d IIB H2 T4 Gb Ta 20 C to 85 C no display Ta 10...

Page 12: ...dards to ensure safe and reliable operation when used as intended Due to its nature this equipment may contain small quantities of substances known to be hazardous to the environment or to human healt...

Reviews: