background image

Doc# 

M9005 • REV N

 (May 2017) Page 

9 of 12

 

Figure 7: 

Auto reset 

CAUTION: 

This test should be performed with the machin

-

ery not running or switch outputs by-passed. After testing, 

reset the limits to the proper operational values.

CAUTION: 

Disconnect or disarm the machine alarms and/or 

shutdown circuits prior to testing the vibration switch outputs.

TROUBLESHOOTING

1. The unit appears to be functioning, but limit operation is in question.

a) Operation of the limit triac/FET and the attached relay can be verified by toggling the NO/

NC switch.

b) The limit setting can be rotated to the minimum (-10%) setting in order to exercise all of 

the limit control logic and trip delay circuits. The limit triac/FET should operate and the limit 

LED should turn on after the set trip delay expires. REMEMBER to return the limit setting to 

the original position after this test.

c) If the LED is lit but the limit is not functioning, check to make sure the triac/FET load is 

wired properly and power is present at the limit terminal block and relay. CAUTION: voltages 

at the limit switch terminal block can be dangerous. Exercise caution when checking for volt

-

age at the terminal block. For AC loads, ensure the minimum current through the load is 35 

mA for temperatures above 25°C or 60 mA below 25°C. For DC loads, ensure proper wiring 

polarity has been observed. 

2. The unit appears to be functioning, but the 4-20 mA operation is in question.

a) Ensure that the current loop is wired properly and that the total loop resistance does not 

exceed 600 ohms. The Model SW6000 4-20 mA circuit is a current source. A voltage source 

(power supply) must not be used in the circuit.

Summary of Contents for SW6000

Page 1: ...s standard configuration the SW6000 is an economical single set point vibration switch with standard features and packaged in industrial grade housing with available haz ardous area certifications Ful...

Page 2: ...d Mount Unit requires a tapped hole see Metrix Datasheet doc 1009462 Option F or use a Metrix model 7084 flange mount adapter If an NPT mounting stud is selected the stud will tighten before the switc...

Page 3: ...ocations NOTES 1 Diagrams show all available options see SW6000 datasheet doc 1009462 to verify options on your particular unit 2 On Single Limit Models use Load Limit Two 2 Baseefa Special Conditions...

Page 4: ...the shield should be tied to common only at the receiver end A cable consist ing of separate shielded twisted pairs can also be used For the dynamic signal output the capacitance of the cable run mus...

Page 5: ...See Figure 2 b M2 M3 and remote reset contacts must each be isolated Figure 4 Parallel connection of two SW6000 a Set each SW6000 for N C normally closed operation See Figure 2 b M2 M3 and remote rese...

Page 6: ...ts if ap plicable 4 20 mA Current Source Output optional If the optional 4 20 mA output is installed it may be connected to a remote receiver as shown on the wiring diagram see Figure 2 This output is...

Page 7: ...re that the analyzer is configured with the same frequency response as the SW6000 and with the same unit of measure i e ips pk To prevent tampering there are no user accessible adjustments available f...

Page 8: ...t will trip The adjustment has a range of 10 to 110 of the full scale vibration level A midscale adjustment corresponds to a 50 vibration level limit The limit setting can be set precisely by measurin...

Page 9: ...it LED should turn on after the set trip delay expires REMEMBER to return the limit setting to the original position after this test c If the LED is lit but the limit is not functioning check to make...

Page 10: ...continuously The limits may need to be reset depending on the particular application Afterwards the machine can be started in a normal fashion 5 The unit is functioning but accuracy is in question a T...

Page 11: ...AS DEBRANCHER TANT QUE LE CIRCUIT EST SOUS TENSION A MOINS QU IL NE S AGISSE D UN EMPLACEMENT NON DAN GEREUX ATEX Approval Europe ATEX Markings II 2G Ex d IIB H2 T4 Gb Ta 20 C to 85 C no display Ta 10...

Page 12: ...dards to ensure safe and reliable operation when used as intended Due to its nature this equipment may contain small quantities of substances known to be hazardous to the environment or to human healt...

Reviews: