MR-GW User Manual | EN
V 1.0 | Version 05/2020
Page 11 of 29
METZ CONNECT GmbH | Im Tal 2 | 78176 Blumberg | Deutschland
Tel. +49 7702 533-0 | Fax +49 7702 533-433
more Documentation: www.metz-connect.com
3.6
Communication interfaces
3.6.1
Ethernet interface
The Ethernet interface of the MR-GW supports the following specifications:
RJ-45 connector for Ethernet connection
10Base-T and 100BASE-T with auto-negotiation
The software tool
MC-Search Utility
for Windows is provided for device search and configuration
Configurable with Telnet network utility.
Number of clients connected simultaneously (master devices) MODBUS TCP: 32
Number of clients connected simultaneously (master devices) MODBUS RTU Over TCP: 1.
3.7
Ports
Description
Port
MODBUS TCP/IP Server network port
502
MODBUS RTU over TCP-Server network port 4001
Webserver network port
80
Telnet Server network port
23
Broadcast search Server port
1030
3.8
Timeout
The TCP/IP connection timeout to MODBUS RTU Over TCP is 60 seconds. When a client connection is
established in MODBUS RTU Over TCP mode, a connection from another IP address is only possible if the
existing connection is inactive during the specified timeout.
3.9
RS-485 interface
Description
Parameter
Data bits
8
Supported baud rates
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Parity
None, Even, Odd
Stop bits
1 or 2
Galvanic isolation
1,5 kV